294 Actual signals and parameters
8402 SEQ PROG
START
Selects the source for the Sequence programming
activation signal.
When Sequence programming is activated, the
programming starts from the previously used state.
If Sequence programming activation signal is lost, the
Sequence programming is stopped and all timers and
outputs (RO/TO/AO) are set to zero. Sequence
programming state (
) remains
unchanged.
If start from the first Sequence programming state is
required, the Sequence programming must be reset by
parameter
. If start from the first
Sequence programming state is always required, reset and
start signal sources (
and
)
must be through the same digital input.
Note
: The drive will not start if no Run enable signal is
received (
).
DI1(INV)
Sequence programming activation through inverted digital
input DI1. 0 = active, 1 = inactive.
-1
DI2(INV)
See selection
-2
DI3(INV)
See selection
-3
DI4(INV)
See selection
-4
DI5(INV)
See selection
-5
NOT SEL
No Sequence programming activation signal
0
DI1
Sequence programming activation through digital input DI1.
1 = active, 0 = inactive.
1
DI2
See selection
2
DI3
See selection
3
DI4
See selection
4
DI5
See selection
5
DRIVE START Sequence programming activation at drive start
6
TIMED FUNC 1 Sequence programming is activated by timed function 1.
See parameter group
7
TIMED FUNC 2 See selection
.
8
TIMED FUNC 3 See selection
.
9
TIMED FUNC 4 See selection
.
10
RUNNING
Sequence programming is always active.
11
All parameters
No.
Name/Value
Description
Def/FbEq
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...