316 Fieldbus control with embedded fieldbus
The new settings will take effect when the drive is next powered up, or when
parameter
setting is cleared and reset.
Drive control parameters
After the Modbus communication has been set up, the drive control parameters listed
in the table below should be checked and adjusted when necessary.
The
Setting for fieldbus control
column gives the value to use when the Modbus
interface is the desired source or destination for that particular signal. The
Function/Information
column gives a description of the parameter.
Parameter
Setting for
fieldbus
control
Function/Information
Modbus register
address
CONTROL COMMAND SOURCE SELECTION
ABB
DRV
DCU
bits
0…1 (
) when EXT1 is
selected as the active control
location.
40031
bits 0…1
bits
0…1 (
) when EXT2 is
selected as the active control
location.
40031
bits 0…1
Enables the rotation direction control
as defined by parameters
and
. The direction control is
explained in section
on page
.
40031
bit 2
Enables jogging 1 or 2 activation
through
bits
20…21 (
.
40032
bits
20…21
Enables EXT1/EXT2 selection
through
bit 5
(
); with the ABB drives profile
bit 11 (
40001
bit 11
40031
bit 5
Fieldbus reference REF1 is used
when EXT1 is selected as the active
control location. See section
for
information on the alternative
settings.
40002 for REF1
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...