Technical data 379
Type
ACS355-
Input
Amps
Frame
size
MMP type E
1,2)
Min. encl. vol.
5)
dm
3
cu in
1-phase
U
N
= 200
…
240 V
(200, 208, 220, 230, 240 V)
01x-02A4-2
6.1
R0
MS132-6.3 & S1-M3-25
3)
18.9
1152
01x-04A7-2
11.0
R1
MS165-16
18.9
1152
01x-06A7-2
16.0
R1
MS165-20
18.9
1152
01x-07A5-2
17.0
R2
MS165-20
-
-
01x-09A8-2
21.0
R2
MS165-25
-
-
3-phase
U
N
= 200
…
240 V
(200, 208, 220, 230, 240 V)
4)
03x-02A4-2
4.3
R0
MS132-6.3 & S1-M3-25
3)
18.9
1152
03x-03A5-2
6.1
R0
MS132-6.3 & S1-M3-25
3)
18.9
1152
03x-04A7-2
7.6
R1
MS132-10 & S1-M3-25
3)
18.9
1152
03x-06A7-2
11.8
R1
MS165-16
18.9
1152
03x-07A5-2
12.0
R1
MS165-16
18.9
1152
03x-09A8-2
14.3
R2
MS165-16
-
-
03x-13A3-2
22.0
R2
MS165-25
-
-
03x-17A6-2
25.0
R2
MS165-32
-
-
03x-24A4-2
41.0
R3
MS165-54
-
-
03x-31A0-2
50.0
R4
MS165-65
-
-
03x-46A2-2
69.0
R4
MS5100-100
-
-
3-phase
U
N
= 380, 400, 415 V
4)
03x-01A2-4
2.2
R0
MS132-2.5 & S1-M3-25
3)
18.9
1152
03x-01A9-4
3.6
R0
MS132-4.0 & S1-M3-25
3)
18.9
1152
03x-02A4-4
4.1
R1
MS132-6.3 & S1-M3-25
3)
18.9
1152
03x-03A3-4
6.0
R1
MS132-6.3 & S1-M3-25
3)
18.9
1152
03x-04A1-4
6.9
R1
MS132-10 & S1-M3-25
3)
18.9
1152
03x-05A6-4
9.6
R1
MS132-10 & S1-M3-25
3)
18.9
1152
03x-07A3-4
12.0
R1
MS165-16
18.9
1152
03x-08A8-4
14.0
R1
MS165-16
18.9
1152
03x-12A5-4
19.0
R3
MS165-20
-
-
03x-15A6-4
22.0
R3
MS165-25
-
-
03x-23A1-4
31.0
R3
MS165-32
-
-
03x-31A0-4
52.0
R4
MS165-65
-
-
03x-38A0-4
61.0
R4
MS165-65
-
-
03x-44A0-4
67.0
R4
MS5100-100
-
-
3-phase
U
N
= 440, 460, 480 V
4)
03x-01A2-4
1.8
R0
MS132-2.5 & S1-M3-25
3)
18.9
1152
03x-01A9-4
3.0
R0
MS132-4.0 & S1-M3-25
3)
18.9
1152
03x-02A4-4
3.4
R1
MS132-4.0 & S1-M3-25
3)
18.9
1152
03x-03A3-4
5.0
R1
MS132-6.3 & S1-M3-25
3)
18.9
1152
03x-04A1-4
5.8
R1
MS132-6.3 & S1-M3-25
3)
18.9
1152
03x-05A6-4
8.0
R1
MS132-10 & S1-M3-25
3)
18.9
1152
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...