382 Technical data
Losses, cooling data and noise
Losses and cooling data
Frame size R0 has natural convection cooling. Frame sizes R1…R4 are provided
with an internal fan. The air flow direction is from bottom to top.
The table below specifies the heat dissipation in the main circuit at nominal load and
in the control circuit with minimum load (I/O and panel not in use) and maximum load
(all digital inputs in the on state and the panel, fieldbus and fan in use). The total heat
dissipation is the sum of the heat dissipation in the main and control circuits.
Type
Heat dissipation
Air flow
ACS355-
Main circuit
Control circuit
x = E/U
Rated /
1N
and /
2N
Min
Max
W
W
W
m
3
/h
ft
3
/min
1-phase
U
N
= 200
…
240 V
(200, 208, 220, 230, 240 V)
01x-02A4-2
25
6.1
22.7
-
-
01x-04A7-2
46
9.5
26.4
24
14
01x-06A7-2
71
9.5
26.4
24
14
01x-07A5-2
73
10.5
27.5
21
12
01x-09A8-2
96
10.5
27.5
21
12
3-phase
U
N
= 200
…
240 V
(200, 208, 220, 230, 240 V)
03x-02A4-2
19
6.1
22.7
-
-
03x-03A5-2
31
6.1
22.7
-
-
03x-04A7-2
38
9.5
26.4
24
14
03x-06A7-2
60
9.5
26.4
24
14
03x-07A5-2
62
9.5
26.4
21
12
03x-09A8-2
83
10.5
27.5
21
12
03x-13A3-2
112
10.5
27.5
52
31
03x-17A6-2
152
10.5
27.5
52
31
03x-24A4- 2
250
16.6
35.4
71
42
03x-31A0-2
270
33.4
57.8
96
57
03x-46A2-2
430
33.4
57.8
96
57
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...