Start-up, control with I/O and ID run 65
Permanent magnet synchronous motor
nameplate example:
• motor nominal voltage (parameter
).
For permanent magnet synchronous motors, enter
the back emf voltage at nominal speed here.
Otherwise use nominal voltage and perform ID run.
If the voltage is given as voltage per rpm, eg, 60 V
per 1000 rpm, the voltage for 3000 rpm nominal
speed is 3
·
60 V = 180 V.
• nominal motor current
)
Allowed range: 0.2…2.0 ·
I
2N
A
• motor nominal frequency (parameter
• motor nominal speed (parameter
)
• motor nominal power (parameter
)
REM
PAR
FWD
REM