ACS850 More parameters read from drive to PLC
Parameter
Description
Setting
Comment
52.03
…
52.12
Actual value or
parameter of drive
GGii
GG = parameter group, ii = parameter index
Example, 0104 = actual current; 0117 = motor temp 1
51.27
FBA PAR
REFRESH
REFRESH
Updates fieldbus settings (groups 50 to 53)
ACS850 More parameters written from PLC to drive
Parameter
Description
Setting
Comment
53.03
…53.12
Parameter of
drive
GGii
GG = parameter group, ii = parameter index
Example, 2202 = acceleration time 1
51.27
FBA PAR
REFRESH
REFRESH
Updates fieldbus settings (groups 50 to 53)
Configuring ACS880 drives
Starting ACS880 drives for PROFIBUS DP
1. Power up the drive.
2. Enable the communication between the adapter module and the drive by setting parameter
50.01
FBA A Enable
to Enable.
3. Select how the drive reacts to a fieldbus communication break with parameter
50.02 FBA A comm
loss func
.
Note:
This function monitors both communication between the fieldbus master and the adapter
module and communication between the adapter module and the drive.
4. Define the time between communication break detection and the selected action with parameter
50.03 FBA A comm loss t out
.
5. Select application-specific values for the rest of the parameters in group 50, starting from
50.04
.
6. Set the FPBA-01 configuration parameters in group 51. At the minimum, set the required node
address in parameter
51.02 Node address
and the communication profile in
51.05
= 1 (ABB drives).
7. Define the process data transferred to and from the drive in FBA-01 configuration parameter groups
52 and 53.
Note:
The adapter module sets the Status word and Control word automatically in parameters
52.01
and
53.01
.
8. Validate the settings made in parameter groups 51, 52 and 53 by setting parameter
51.27 FBA par
refresh
to Configure.
9. Save the valid parameter values to permanent memory by setting parameter
96.07 Param save
to
Save.
10. Set the relevant drive control parameters to control the drive according to the application.