9
Target audience
This guide is intended for a personnel configuring drive functional blocks. The reader of the guide is
expected to have basic knowledge of the drive technology and programmable devices (PLC, drive and
PC) and programming methods.
Safety instructions
Follow all safety instructions delivered with the drive.
Read the complete safety instructions
before you load and execute the application
program on the drive or modify the drive parameters. The complete safety instructions are
delivered with the drive as either part of the hardware manual, or, in the case of ACS880
multidrives, as a separate document.
Read the firmware function-specific warnings and notes
before changing parameter
values. These warnings and notes are included in the parameter descriptions presented in
chapter
Parameters
of the firmware manual.
WARNING!
Ignoring the following instruction can cause physical injury or damage to
the equipment.
Do not make changes to drive in the online mode or download programs while the
drive is running to avoid damages to the drive.
Purpose of the manual
This manual gives basic instructions to configure drive functional blocks with external PLCs. The guide
contains detailed information of the configuring methods.
Limitations
The following limitations are valid for this guide:
The drive must be equipped with PROFIBUS or PROFINET adapters
PROFIBUS DP protocol: DP-V0 or DP-V1
PROFIBUS DP communication profile: ABB drives
All PROFIBUS DP, PROFINET and compatible ABB drives
Application types: Speed/Frequency control or Torque control
Supports PPO types with consistent data, example, PPO-06, 0 PKW + 10 PZD
All the libraries are encrypted with a passcode. If you want to edit the libraries, contact your local
ABB representative for passcode.
Notes:
PPO types without consistent data, example, PPO-06, 0 PKW + (2+2+2+2+2) PZD or PPO-06, 0
PKW +NoCons. 10 PZD are
not
supported by
ABB_DRIVE_LIB
.
The
ABB_DRIVES_LIB
can also be used for PROFINET control of ABB drives. When
programming the function blocks, consider the drive as a PROFIBUS DP-V1 slave.
The hardware configuration (GSDML files) and the drive parameter settings for PROFINET slaves
differ from PROFIBUS slaves.