Actual signals and parameters 225
COMM
Fieldbus interface as the source for the torque limit 1/2
selection, ie, Control word
bit 15.
The Control word is sent by the fieldbus controller through
the fieldbus adapter or embedded fieldbus (Modbus) to the
drive. For the Control word bits, see section
on page
Maximum torque limit 1 is defined by parameter
and maximum torque limit 2 is defined by
parameter
Note:
This setting applies only for the DCU profile.
7
EXT2
11
DI1(INV)
Inverted digital input DI1. 1 = parameter
value. 0 = parameter
value.
-1
DI2(INV)
See selection
.
-2
DI3(INV)
See selection
.
-3
DI4(INV)
See selection
.
-4
DI5(INV)
See selection
.
-5
2015 MIN TORQUE
1
Defines minimum torque limit 1 for the drive. See parameter
-300%
-600.0…0.0%
Value as a percentage of the motor nominal torque
1 = 0.1%
2016 MIN TORQUE
2
Defines minimum torque limit 2 for the drive. See parameter
-300%
-600.0…0.0%
Value as a percentage of the motor nominal torque
1 = 0.1%
2017 MAX TORQUE
1
Defines maximum torque limit 1 for the drive. See
parameter
300%
0.0…600.0%
Value as a percentage of the motor nominal torque
1 = 0.1%
2018 MAX TORQUE
2
Defines maximum torque limit 2 for the drive. See
parameter
300%
0.0…600.0%
Value as a percentage of the motor nominal torque
1 = 0.1%
All parameters
No.
Name/Value
Description
Def/FbEq
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...