Actual signals and parameters 261
3205 SUPERV 2 LIM
LO
Defines the low limit for the second supervised signal
selected by parameter
.
Supervision wakes up if the value is below the limit.
-
x…x
Setting range depends on parameter
setting.
-
3206 SUPERV 2 LIM
HI
Defines the high limit for the second supervised signal
selected by parameter
.
Supervision wakes up if the value is above the limit.
-
x…x
Setting range depends on parameter
setting.
-
3207 SUPERV 3
PARAM
Selects the third supervised signal. Supervision limits are
defined by parameters
and
. See parameter
.
105
x…x
Parameter index in group
. For
example, 102 =
1 = 1
3208 SUPERV 3 LIM
LO
Defines the low limit for the third supervised signal selected
by parameter
. Supervision wakes
up if the value is below the limit.
-
x…x
Setting range depends on parameter
setting.
-
3209 SUPERV 3 LIM
HI
Defines the high limit for the third supervised signal selected
by parameter
. Supervision wakes
up if the value is above the limit.
-
x…x
Setting range depends on parameter
setting.
-
33 INFORMATION
Firmware package version, test date etc.
3301 FIRMWARE
Displays the version of the firmware package.
0000…FFFF
hex
For example, 241A hex
3302 LOADING
PACKAGE
Displays the version of the loading package.
type
dependent
2201…22FF
hex
2201 hex = ACS355-0nE-
2202 hex = ACS355-0nU-
3303 TEST DATE
Displays the test date.
00.00
Date value in format YY.WW (year, week)
3304 DRIVE RATING Displays the drive current and voltage ratings.
0000 hex
0000…FFFF
hex
Value in format XXXY hex:
XXX = Nominal current of the drive in amperes. An “A”
indicates decimal point. For example if XXX is 9A8, nominal
current is 9.8 A.
Y = Nominal voltage of the drive:
1 = 1-phase 200…240 V
2 = 3-phase 200…240 V
4 = 3-phase 380…480 V
All parameters
No.
Name/Value
Description
Def/FbEq
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...