Actual signals and parameters 301
8423 ST1 OUT
CONTROL
Selects the relay, transistor and analog output control for
Sequence programming state 1.
The relay/transistor output control must be activated by
setting parameter
to
. Analog output control must be
activated by parameter group
Analog output control values can be monitored with signal
RO2=RO3
=RO4=1
Relay outputs are energized (closed). Effective only with the
MREL-01 option.
-1.5
RO2=1, RO3=1 Relay outputs are energized (closed). Effective only with the
MREL-01 option.
-1.4
RO4 = 1
Relay output is energized (closed). Effective only with the
MREL-01 option.
-1.3
RO3 = 1
Relay output is energized (closed). Effective only with the
MREL-01 option.
-1.2
RO2 = 1
Relay output is energized (closed). Effective only with the
MREL-01 option.
-1.1
RST CNT
NEXT
Reserved for Enhanced Sequence Program (ESP).
-1.0
RST CNT ENT Reserved for ESP.
-0.8
RST CNT
STNX
Reserved for ESP.
-0.9
R=0,D=1,AO=0 Relay output is de-energized (opened), transistor output is
energized and analog output is cleared.
-0.7
R=1,D=0,AO=0 Relay output is energized (closed), transistor output is de-
energized and analog output is cleared.
-0.6
R=0,D=0,AO=0 Relay and transistor outputs are de-energized (opened) and
analog output value is set to zero.
-0.5
RO=0,DO=0
Relay and transistor outputs are de-energized (opened) and
analog output control is frozen to the previously set value.
-0.4
RO=1,DO=1
Relay and transistor outputs are energized (closed) and
analog output control is frozen to the previously set value.
-0.3
DO=1
Transistor output is energized (closed) and relay output is
de-energized. Analog output control is frozen to the
previously set value.
-0.2
RO=1
Transistor output is de-energized (opened) and relay output
is energized. Analog output control is frozen to the
previously set value.
-0.1
All parameters
No.
Name/Value
Description
Def/FbEq
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...