Technical data 389
Ambient conditions
Environmental limits for the drive are given below. The drive is to be used in a heated indoor
controlled environment.
Operation
installed for
stationary use
Storage
in the protective
package
Transportation
in the protective
package
Installation site altitude
0…2000 m (6600 ft)
above sea level
(above 1000 m
[3300 ft], see section
on page
-
-
Air temperature
-10 … +50 °C
(14 … 122 °F).
No frost allowed. See
section
on
page
-40 … +70 °C ±2%
(-40 … +158 °F ±2%)
-40 … +70 °C ±2%
(-40 … +158 °F ±2%)
Relative humidity
0 … 95%
Max. 95%
Max. 95%
No condensation allowed. Maximum allowed relative humidity is
60% in the presence of corrosive gases.
Contamination levels
(IEC 60721-3-3,
IEC 60721-3-2,
IEC 60721-3-1)
No conductive dust allowed.
According to
IEC 60721-3-3,
chemical gases:
Class 3C2
solid particles:
Class 3S2.
Note:
The drive must
be installed in clean
air according to
enclosure
classification.
Note:
Cooling air
must be clean, free
from corrosive
materials and
electrically conductive
dust.
According to
IEC 60721-3-1,
chemical gases:
Class 1C2
solid particles:
Class 1S2
According to
IEC 60721-3-2,
chemical gases:
Class 2C2
solid particles:
Class 2S2
Sinusoidal vibration
(IEC 60721-3-3)
Tested according to
IEC 60721-3-3,
mechanical
conditions: Class 3M4
2…9 Hz, 3.0 mm
(0.12 in)
9…200 Hz, 10 m/s
2
(33 ft/s
2
)
-
-
Summary of Contents for ACS355 series
Page 1: ...ABB machinery drives User s manual ACS355 drives ...
Page 4: ......
Page 16: ...16 ...
Page 32: ...32 Operation principle and hardware description ...
Page 58: ...58 Electrical installation ...
Page 74: ...74 Start up control with I O and ID run ...
Page 106: ...106 Control panels ...
Page 120: ...120 Application macros ...
Page 178: ...178 Program features ...
Page 338: ...338 Fieldbus control with embedded fieldbus ...
Page 368: ...368 Fault tracing ...
Page 404: ...404 Dimension drawings ...
Page 410: ...410 Appendix Resistor braking ...
Page 434: ...434 Appendix Permanent magnet synchronous motors PMSMs ...