UL (NEC) fuses
Fuses
Drive in-
put cur-
rent
UL (NEC)
type
ACS480-
04-…
Max. fuse rating
for group install-
ation
1)
Type
Bussmann/
Edison type
Voltage
rating
Nomin-
al cur-
rent
A
V
A
A
1-phase
U
N = 230 V
10
UL class T
JJN/TJN10
300
10
5.0
02A3-1
10
UL class T
JJN/TJN10
300
10
7.8
03A5-1
25
UL class T
JJN/TJN20
300
20
10.1
04A6-1
25
UL class T
JJN/TJN20
300
20
14.5
06A6-1
25
UL class T
JJN/TJN25
300
25
16.4
07A4-1
35
UL class T
JJN/TJN25
300
25
20.6
09A3-1
35
UL class T
JJN/TJN35
300
35
25.6
11A6-1
3-phase
U
N = 230 V
25
UL class T
JJS/TJS6
600
6
3.6
02A3-2
25
UL class T
JJS/TJS10
600
10
5.6
03A5-2
25
UL class T
JJS/TJS10
600
10
7.2
04A6-2
25
UL class T
JJS/TJS20
600
20
10.4
06A6-2
25
UL class T
JJS/TJS20
600
20
11.7
07A5-2
30
UL class T
JJS/TJS25
600
25
18.3
11A6-2
40
UL class T
JJS/TJS35
600
35
24.6
017A-2
40
UL class T
JJS/TJS40
600
40
35.1
024A-2
100
UL class T
JJS/TJS60
600
60
45.0
031A-2
100
UL class T
JJS/TJS100
600
100
57.6
046A-2
100
UL class T
JJS/TJS100
600
100
60.0
053A-2
3-phase
U
N = 480 V
25
UL class T
JJS/TJS6
600
6
4.2
02A1-4
25
UL class T
JJS/TJS6
600
6
5.3
03A0-4
25
UL class T
JJS/TJS10
600
10
6.4
03A5-4
25
UL class T
JJS/TJS10
600
10
9.0
04A8-4
25
UL class T
JJS/TJS20
600
20
11.5
06A0-4
25
UL class T
JJS/TJS20
600
20
15.0
07A6-4
30
UL class T
JJS/TJS25
600
25
20.2
011A-4
40
UL class T
JJS/TJS35
600
35
27.2
014A-4
40
UL class T
JJS/TJS40
600
40
40.0
021A-4
100
UL class T
JJS/TJS60
600
60
45.0
027A-4
Technical data 139
Summary of Contents for ACS480-04-09A8-1
Page 1: ... ABB GENERAL PURPOSE DRIVES ACS480 drives Hardware manual ...
Page 2: ......
Page 4: ......
Page 14: ...14 ...
Page 22: ...22 ...
Page 28: ...28 ...
Page 38: ...38 ...
Page 44: ...44 ...
Page 118: ...118 ...
Page 126: ...126 ...
Page 174: ...174 ...
Page 176: ...Frame R0 Frame R0 front side IP20 UL open type 176 Dimension drawings ...
Page 177: ... Frame R0 bottom rear IP20 UL open type Dimension drawings 177 ...
Page 178: ...Frame R1 Frame R1 front side IP20 UL open type 178 Dimension drawings ...
Page 179: ... Frame R1 bottom rear IP20 UL open type Dimension drawings 179 ...
Page 180: ... Frame R1 front side UL Type 1 kit installed 180 Dimension drawings ...
Page 181: ... Frame R1 bottom rear UL Type 1 kit installed Dimension drawings 181 ...
Page 182: ...Frame R2 Frame R2 front side IP20 UL open type 182 Dimension drawings ...
Page 183: ... Frame R2 bottom rear IP20 UL open type Dimension drawings 183 ...
Page 184: ... Frame R2 front side UL Type 1 kit installed 184 Dimension drawings ...
Page 185: ... Frame R2 bottom rear UL Type 1 kit installed Dimension drawings 185 ...
Page 186: ...Frame R3 Frame R3 front side IP20 UL open type 186 Dimension drawings ...
Page 187: ... Frame R3 bottom rear IP20 UL open type Dimension drawings 187 ...
Page 188: ... Frame R3 front side UL Type 1 kit installed 188 Dimension drawings ...
Page 189: ... Frame R3 bottom rear UL Type 1 kit installed Dimension drawings 189 ...
Page 190: ...Frame R4 Frame R4 front side IP20 UL open type 190 Dimension drawings ...
Page 191: ... Frame R4 bottom rear IP20 UL open type Dimension drawings 191 ...
Page 192: ... Frame R4 front side UL Type 1 kit installed 192 Dimension drawings ...
Page 193: ... Frame R4 bottom rear UL Type 1 kit installed Dimension drawings 193 ...
Page 194: ...194 ...
Page 221: ... Declarations of conformity The Safe torque off function 221 ...
Page 231: ...Dimensions BIO 01 I O extension module 231 ...
Page 232: ...232 ...
Page 238: ...Dimensions 3AXD50000031148 rev A 238 BREL 01 relay output extension module ...