ACS510 User’s Manual
101
Start-Up
Group 30: Fault Functions
This group defines situations that the drive should recognize as potential faults and
defines how the drive should respond if the fault is detected.
Code Description
3001
AI<MIN FUNCTION
Defines the drive response if the analog input (
AI
) signal drops below the fault limits and
AI
is used in reference chain.
3021
AI
1
FAULT
LIMIT
and 3022
AI
2
FAULT
LIMIT
set the fault limits
0 =
NOT
SEL
– No response.
1 =
FAULT
– Displays a fault (7,
AI
1
LOSS
or 8,
AI
2
LOSS
) and the drive coasts to stop.
2 =
CONST
SP
7 – Displays an alarm (2006,
AI
1
LOSS
or 2007,
AI
2
LOSS
) and sets speed using 1208
CONST
SPEED
7.
3 =
LAST
SPEED
– Displays an alarm (2006,
AI
1
LOSS
or 2007,
AI
2
LOSS
) and sets speed using the last operating level.
This value is the average speed over the last 10 seconds.
Warning!
If you select
CONST
SP
7 or
LAST
SPEED
, make sure that continued operation is safe when the analog input
signal is lost.
3002
PANEL COMM ERR
Defines the drive response to a control panel communication error.
1 =
FAULT
– Displays a fault (10,
PANEL
LOSS
) and the drive coasts to stop.
2 =
CONST
SP
7 – Displays an alarm (2008,
PANEL
LOSS
) and sets speed using 1208
CONST
SPEED
7.
3 =
LAST
SPEED
– Displays an alarm (2008,
PANEL
LOSS
) and sets speed using the last operating level. This value is
the average speed over the last 10 seconds.
Warning!
If you select
CONST
SP
7 or
LAST
SPEED
, make sure that continued operation is safe when the control panel
communication is lost.
3003
EXTERNAL FAULT 1
Defines the External Fault 1 signal input and the drive response to an external fault.
0 =
NOT
SEL
– External fault signal is not used.
1 =
DI
1 – Defines digital input
DI
1 as the external fault input.
• Activating the digital input indicates a fault. The drive displays a fault (14,
EXT
FAULT
1) and the drive coasts to
stop.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as the external fault input.
• See
DI
1 above.
-1 =
DI
1(
INV
) – Defines an inverted digital input
DI
1 as the external fault input.
• De-activating the digital input indicates a fault. The drive displays a fault (14,
EXT
FAULT
1) and the drive coasts to
stop.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6 as the external fault input.
• See
DI
1(
INV
) above.
3004
EXTERNAL FAULT 2
Defines the External Fault 2 signal input and the drive response to an external fault.
• See parameter 3003 above.
3005
MOT THERM PROT
Defines the drive response to motor overheating.
0 =
NOT
SEL
– No response and/or motor thermal protection not set up.
1 =
FAULT
– When the calculated motor temperature exceeds 90 C, displays an alarm (2010,
MOTOR
TEMP
). When the
calculated motor temperature exceeds 110 C, displays a fault (9,
MOT
OVERTEMP
) and the drive coasts to stop.
2 =
ALARM
– When the calculated motor temperature exceeds 90 C, displays an alarm (2010,
MOTOR
TEMP
).
3006
MOT THERM TIME
Sets the motor thermal time constant for the motor temperature
model.
• This is the time required for the motor to reach 63% of the final
temperature with steady load.
• For thermal protection according to UL requirements for NEMA
class motors, use the rule of thumb:
MOTOR
THERM
TIME
equals
35 times t6, where t6 (in seconds) is specified by the motor
manufacturer as the time that the motor can safely operate at six
times its rated current.
• The thermal time for a Class 10 trip curve is 350 s, for a Class
20 trip curve 700 s, and for a Class 30 trip curve 1050 s.
Temp. Rise
100%
63%
t
t
}
P 3006
Motor load