122
ACS510 User’s Manual
Start-Up
Group 42: External / Trimming PID
This group defines the parameters used for the second PID controller (PID2), which
is used for the External / Trimming PID.
The operation of parameters 4201
…
4221 is analogous with Process PID set 1
(PID1) parameters 4001…4021.
Code Description
4201
…
4221
See 4001 …4021
4228
ACTIVATE
Defines the source for enabling the external PID function.
• Requires 4230
TRIM
MODE
= 0
NOT
SEL
.
0 =
NOT
SEL
– Disables external PID control.
1 =
DI
1 – Defines digital input
DI
1 as the control for enabling external PID control.
• Activating the digital input enables external PID control.
• De-activating the digital input disables external PID control.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as the control for enabling external PID control.
• See
DI
1 above.
7 =
DRIVE
RUN
– Defines the start command as the control for enabling external PID control.
• Activating the start command (drive is running) enables external PID control.
8 =
ON
– Defines the power-on as the control for enabling external PID control.
• Activating power to the drive enables external PID control.
-1 =
DI
1(
INV
) – Defines an inverted digital input
DI
1 as the control for enabling external PID control.
• Activating the digital input disables external PID control.
• De-activating the digital input enables external PID control.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6 as the control for enabling external PID control.
• See
DI
1(
INV
) above.
4229
OFFSET
Defines the offset for the PID output.
• When PID is activated, output starts from this value.
• When PID is deactivated, output resets to this value.
• Parameter is active when 4230
TRIM
MODE
= 0 (trim mode is not
active).
4230
TRIM MODE
Selects the type of trim, if any. Using the trim it is possible to combine a corrective factor to the drive reference.
0 =
NOT
SEL
– Disables the trim function.
1 =
PROPORTIONAL
– Adds a trim factor that is proportional to the Hz reference.
2 =
DIRECT
– Adds a trim factor based on the control loop’s maximum limit.
4231
TRIM SCALE
Defines the multiplier (as a percent, plus or minus) used in the trim mode.
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn