128
ACS510 User’s Manual
Start-Up
– Drive waits for PFC Start Delay(parameter 8122). Modulation is not allowed
because drive has to wait that all contactor are stabilized.
– Modulation is allowed. Modulation starts from zero speed. After F
out
rises over
Start Frequency 1, Aux. Mot. Start Delay starts (parameter 8115).
– When Aux. Mot. Start Delay elapses then drive coasts to stop and RO1 is
opened.
– Drive waits for PFC Start Delay (parameter 8122). Meaning of this delay it to
wait contactors to stabilize. If there is some oscillation in Motor 1 contactors
when closing RO2, then contactors might go to wrong state.
– Drive close RO2. This is new plae for Speed Regulated Motor. Modulation is
not allow yet.
– Drive waits for PFC Start Delay (parameter 8122). Modulation is not allowed
because the drive has to wait that all contactors are stabilized.
– Drive close RO1. Motor in RO1 is connected directly to the network(constant
speed) and modulation is allowed. Drive start accelerating from zero in RO2.
• Stoping motors goes like in standard PFC. See the figure.
Start
FOut
RO1 /Motor1
8122 PFC START DLY
8109 START START FREQ 1
RO2 /Motor2
8122 PFC START DLY
Motor in RO1 is Speed Req Motor
Motor in RO2 is Speed Req Motor
Motor in RO1 is Aux Motor
8122 PFC START DLY
1.
2.
3.
4.
5.
6.
7.
8.
Start
RO2 /Motor1
RO1 /Motor2
8109 START LOW FREQ 1
Motor in RO2 is
Speed Req Motor
Motor in RO1 is
Aux Motor
FOut
Speed Req Motor in RO2