ACS510 User’s Manual
157
Embedded Fieldbus
• Relay output states, numbered sequentially beginning with coil 00033.
The following table summarizes the 0xxxx reference set:
*
= Active low
For the 0xxxx registers:
• Status is always readable.
• Forcing is allowed by user configuration of the drive for fieldbus control.
• Additional relay outputs are added sequentially.
Modbus
Ref.
Internal Location
(All Profiles)
ABB
DRV
LIM
(5305 = 0)
DCU
PROFILE
(5305 = 1)
ABB
DRV
FULL
(5305 = 2)
0
0001
CONTROL
WORD
– Bit 0
OFF1*
STOP
OFF1*
0
0002
CONTROL
WORD
– Bit 1
OFF2*
START
OFF2*
0
0003
CONTROL
WORD
– Bit 2
OFF3*
REVERSE
OFF3*
0
0004
CONTROL
WORD
– Bit 3
START
LOCAL
START
0
0005
CONTROL
WORD
– Bit 4
N/A
RESET
RAMP_OUT_ZERO*
0
0006
CONTROL
WORD
– Bit 5
RAMP_HOLD*
EXT2
RAMP_HOLD*
0
0007
CONTROL
WORD
– Bit 6
RAMP_IN_ZERO* RUN_DISABLE
RAMP_IN_ZERO*
0
0008
CONTROL
WORD
– Bit 7
RESET
STPMODE_R
RESET
0
0009
CONTROL
WORD
– Bit 8
N/A
STPMODE_EM
N/A
0
0010
CONTROL
WORD
– Bit 9
N/A
STPMODE_C
N/A
0
0011
CONTROL
WORD
– Bit 10 N/A
RAMP_2
REMOTE_CMD*
0
0012
CONTROL
WORD
– Bit 11 EXT2
RAMP_OUT_0
EXT2
0
0013
CONTROL
WORD
– Bit 12 N/A
RAMP_HOLD
N/A
0
0014
CONTROL
WORD
– Bit 13 N/A
RAMP_IN_0
N/A
0
0015
CONTROL
WORD
– Bit 14 N/A
REQ_LOCALLOCK N/A
0
0016
CONTROL
WORD
– Bit 15 N/A
TORQLIM2
N/A
0
0017
CONTROL
WORD
– Bit 16 Does not apply
FBLOCAL_CTL
Does not apply
0
0018
CONTROL
WORD
– Bit 17
FBLOCAL_REF
0
0019
CONTROL
WORD
– Bit 18
START_DISABLE1
0
0020
CONTROL
WORD
– Bit 19
START_DISABLE2
0
0021…
0
0032
Reserved
Reserved
Reserved
Reserved
0
0033
RELAY
OUTPUT
1
Relay Output 1
Relay Output 1
Relay Output 1
0
0034
RELAY
OUTPUT
2
Relay Output 2
Relay Output 2
Relay Output 2
0
0035
RELAY
OUTPUT
3
Relay Output 3
Relay Output 3
Relay Output 3
0
0036
RELAY
OUTPUT
4
Relay Output 4
Relay Output 4
Relay Output 4
0
0037
RELAY
OUTPUT
5
Relay Output 5
Relay Output 5
Relay Output 5
0
0038
RELAY
OUTPUT
6
Relay Output 6
Relay Output 6
Relay Output 6