ACS510 User’s Manual
3
Safety
Safety
Warning!
The ACS510 adjustable speed AC drive should ONLY be installed by a
qualified electrician.
Warning!
Even when the motor is stopped, dangerous voltage is present at the
Power Circuit terminals U1, V1, W1 and U2, V2, W2 and, depending on the frame
size, UDC+ and UDC-, or BRK+ and BRK-.
Warning!
Dangerous voltage is present when input power is connected. After
disconnecting the supply, wait at least 5 minutes (to let the intermediate circuit
capacitors discharge) before removing the cover.
Warning!
Even when power is removed from the input terminals of the ACS510,
there may be dangerous voltage (from external sources) on the terminals of the relay
outputs R01
…
R03.
Warning!
When the control terminals of two or more drive units are connected in
parallel, the auxiliary voltage for these control connections must be taken from a
single source which can either be one of the units or an external supply.
Warning!
The ACS510-01 is not a field repairable unit. Never attempt to repair a
malfunctioning unit; contact the factory or your local Authorized Service Center for
replacement.
Warning!
The ACS510 will start up automatically after an input voltage interruption if
the external run command is on.
Warning!
The heat sink may reach a high temperature. See "Technical Data" on
page 211.
Warning!
If the drive will be used in a floating network, remove screws at EM1 and
EM3 (Frame size R1
…
R4), or F1 and F2 (Frame size R5 or R6). See diagrams on
page 15 and page 16 respectively. Also see "Unsymmetrically Grounded Networks"
and "Floating Networks" on page 217.
Warning!
Do not attempt to install or remove EM1, EM3, F1 or F2 screws while
power is applied to the drive’s input terminals.
Note!
For more technical information, contact the factory or your local ABB sales
representative.