94
ACS510 User’s Manual
Start-Up
2108
START INHIBIT
Sets the Start inhibit function on or off. The Start inhibit function ignores a pending start command in any of the
following situations (a new start command is required):
• A fault is reset.
• Run Enable (parameter 1601) activates while start command is active.
• Mode changes from local to remote.
• Control switches from
EXT
1 to
EXT
2.
• Control switches from
EXT
2 to
EXT
1.
0 =
OFF
– Disables the Start inhibit function.
1 =
ON
– Enables the Start inhibit function.
2109
EMERG STOP SEL
Defines control of the Emergency stop command. When activated:
• Emergency stop decelerates the motor using the emergency stop ramp (parameter 2208
EMERG DEC TIME
).
• Requires an external stop command and removal of the emergency stop command before drive can restart.
0 =
NOT
SEL
– Disables the Emergency stop function through digital inputs.
1 =
DI
1 – Defines digital input
DI
1 as the control for Emergency stop command.
• Activating the digital input issues an Emergency stop command.
• De-activating the digital input removes the Emergency stop command.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as the control for Emergency stop command.
• See
DI
1 above.
-1 =
DI
1(
INV
) – Defines an inverted digital input
DI
1 as the control for Emergency stop command.
• De-activating the digital input issues an Emergency stop command.
• Activating the digital input removes the Emergency stop command.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6 as the control for Emergency stop command.
• See
DI
1(
INV
) above.
2110
TORQ BOOST CURR
Sets the maximum supplied current during torque boost.
See parameter 2101
START
FUNCTION
.
2113
START DELAY
Defines the Start delay. After the conditions for start have been fulfilled, the drive waits until the delay has elapsed
and then starts the motor. Start delay can be used with all start modes.
• If
START DELAY
=
ZERO
, the delay is disabled.
• During the start delay, alarm 2028
START DELAY
is shown.
Code Description
Supplied from China by: Guangzhou Tofee Electro Mechanical Equipment Co., Ltd
Email: info@tofee.com.cn