Alarm Listing
The following table lists the alarms by code number and describes each.
Alarm
Code
Display
Description
2001
OVERCURRENT
Current limiting controller is active. Check for and correct:
• Excessive motor load.
• Insufficient acceleration time (parameters 2202
ACCELER
TIME
1 and
2205
ACCELER
TIME
2).
• Faulty motor, motor cables or connections.
2002
OVERVOLTAGE
Overvoltage controller is active. Check for and correct:
• Static or transient overvoltages in the input power supply.
• Insufficient deceleration time (parameters 2203
DECELER
TIME
1 and
2206
DECELER
TIME
2).
2003
UNDERVOLTAGE
Undervoltage controller is active. Check for and correct:
• Undervoltage on mains.
2004
DIR
LOCK
The change in direction being attempted is not allowed. Either:
• Do not attempt to change the direction of motor rotation, or
• Change parameter 1003
DIRECTION
to allow direction change (if
reverse operation is safe).
2005
I
/
O
COMM
Fieldbus communication has timed out. Check for and correct:
• Fault setup (3018
COMM
FAULT
FUNC
and 3019
COMM
FAULT
TIME
).
• Communication settings (Group 51 or 53 as appropriate).
• Poor connections and/or noise on line.
2006
AI
1
LOSS
Analog input 1 is lost, or value is less than the minimum setting.
Check:
• Input source and connections
• Parameter that sets the minimum (3021)
• Parameter that sets the Alarm/Fault operation (3001)
2007
AI
2
LOSS
Analog input 2 is lost, or value is less than the minimum setting.
Check:
• Input source and connections
• Parameter that sets the minimum (3022)
• Parameter that sets the Alarm/Fault operation (3001)
2008
PANEL
LOSS
Panel communication is lost and either:
• Drive is in local control mode (the control panel displays LOC), or
• Drive is in remote control mode (REM) and is parameterized to
accept start/stop, direction or reference from the control panel.
To correct check:
• Communication lines and connections
• Parameter 3002
PANEL
COMM
ERR
.
• Parameters in groups 10
COMMAND
INPUTS
and 11
REFERENCE
SELECT
(if drive operation is REM).