18
EN
Connecting control wires
Internal (1) or external (2) power supply can be used for the digital
inputs. Analogue control voltage is 0…10 VDC as default. (The AI
jumper must be in voltage ("U") position).
Control terminals
• Conductor size: stranded 0.25…1.5 mm
2
(AWG 23 to AWG 16)
• Tightening torque: 0.25 N·m.
1) Connected internally to frame (earth) through 1 Mohm resistor.
2) Digital input impedance is 1.5 kohm.
Using 0/4…20 mA current signal:
- Change AI jumper to current
("I") position.
- Set AI OFFSET switch to ON
position if 4…20 mA current
signal is desired.
SCR
ST
AR
T
REV
JOG
+
-
2)
1)
U
I
12...24 VDC supply
+12V
COM
SPEED/AI
+10V
COM
SCR
ST
AR
T
REV
JOG
+12V
COM
SPEED/AI
+10V
COM
AI
U
I
AI
SCR
START
REV
JOG
+12V
COM
SPEED/AI
+10V
COM
+
-
1...10 kohm
#
Name
Description
1
COM
Common for digital or analogue inputs
1)
2
COM
Common for digital or analogue input
1)
3
AI
Analogue input: Speed (frequency) reference.
0/2…10 VDC (Ri=190 kohm), or 0/4…20 mA
(Ri=100 ohm). Resolution 0.1%, ac/-1%.
4
+10V
Reference voltage for analogue input.
Ac/-2%. Max. 10 mA.
5
+12V
Auxiliary voltage for digital inputs. Max. 30 mA.
6
START Digital input 1: Start (resets the drive after a fault
trip)
2)
7
REV
Digital input 2: Reverse rotation direction
2)
8
JOG
Digital input 3: Activate jog speed
2)
9
SCR
Earth for signal cable screen. Connected internally
to frame earth.
Relay output
1
RO1
Fault: Relay opens.12 V...250 VAC / 30 VDC
10 mA...2 A
2
RO2