Technical data
* Allowed for 1 minute.
** Recommended values. Do not use ultra rapid or low peak fuses. Follow local rules.
230 V
115 V
Built-in EMC, ACS55-01E-
01A4-2
02A2-2
04A3-2
07A6-2
09A8-2
01A4-1
02A2-1
No EMC, ACS55-01N-
01A4-2
02A2-2
04A3-2
07A6-2
09A8-2
01A4-1
02A2-1
Motor continuous output power
kW
0.18
0.37
0.75
1.5
2.2
0.18
0.37
hp
1/4
1/2
1
2
3
1/4
1/2
Frame size (no EMC)
A
A
B
C
C
A
A
Frame size (EMC)
A
A
B
D
D
A
A
Nominal ratings
Input voltage
U
1
V
200…240 (+10/-15%)
110…120 (+10/-15%)
Continuous output current
I
2
A
1.4
2.2
4.3
7.6
9.8
1.4
2.2
Max. output current
I
2max
*
A
2.1
3.3
6.5
11.4
14.7
2.1
3.3
Output voltage
U
2
V
0…
U
1
, 3-phase
0…2×
U
1
, 3-phase
Input current
I
1
A
4.4
6.9
10.8
18.2
22.0
6.4
9.5
Switching frequency
kHz
5 (max. 16)
Protection limits
Overcurrent (peak)
A
4.4
6.9
13.5
23.9
30.9
4.4
6.9
Overtemperature
95°C / 203°F (heat sink)
Maximum wire sizes
Power terminals
mm
2
2.5 (AWG 14)
4 (AWG 12)
2.5 (AWG 14)
Control terminals
mm
2
1.5 (AWG 16)
Power losses
W
21
32
51
74
103
24
35
Line fuse size**
IEC, type IEC269 gG
A
10
16
16
25
32
10
16
UL, types CC and T
A
10
15
20
25
30
10
15
Weight, Built-in EMC, ACS55-01E-
kg (lb)
0.65 (1.4)
0.7 (1.5)
0.9 (2)
1.6 (3.5)
1.7 (3.7)
0.65 (1.4)
0.7 (1.5)
Weight, No EMC, ACS55-01N-
kg (lb)
0.65 (1.4)
0.7 (1.5)
0.9 (2)
1.2 (2.6)
1.3 (2.9)
0.65 (1.4)
0.7 (1.5)
GHV Vertriebs-GmbH • 85567 Grafing • Tel: +49 (0) 8092 8189 0 • Fax: +49 (0) 8092 8189 99 • info@ghv.de • www.ghv.de