ACS550-02/U2 User’s Manual
145
Parameters
Group 13: ANALOG INPUTS
This group defines the limits and the filtering for analog inputs.
Code Description
1301
MINIMUM AI1
Defines the minimum value of the analog input.
• Define value as a percent of the full analog signal range. See example below.
• The minimum analog input signal corresponds to 1104
REF
1
MIN
or 1107
REF
2
MIN
.
•
MINIMUM
AI
cannot be greater than
MAXIMUM
AI
.
• These parameters (reference and analog min. and max. settings) provide scale and offset adjustment for the
reference.
• See the figure at parameter 1104.
Example.
To set the minimum analog input value to 4 mA:
• Configure the analog input for 0…20 mA current signal.
• Calculate the minimum (4 mA) as a percent of full range (20 mA) = 4 mA / 20 mA · 100% = 20%
1302
MAXIMUM AI1
Defines the maximum value of the analog input.
• Define value as a percent of the full analog signal range.
• The maximum analog input signal corresponds to 1105
REF
1
MAX
or 1108
REF
2
MAX
.
• See the figure at parameter 1104.
1303
FILTER AI1
Defines the filter time constant for analog input 1 (
AI
1).
• The filtered signal reaches 63% of a step change within the time
specified.
1304
MINIMUM AI2
Defines the minimum value of the analog input.
• See
MINIMUM
AI
1 above.
1305
MAXIMUM AI2
Defines the maximum value of the analog input.
• See
MAXIMUM
AI
1 above.
1306
FILTER AI2
Defines the filter time constant for analog input 2 (
AI
2).
• See
FILTER
AI
1 above.
100
63
%
Unfiltered signal
Filtered signal
Time constant
t
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com