ACS550-02/U2 User’s Manual
149
Parameters
Group 15: ANALOG OUTPUTS
This group defines the drive’s analog (current signal) outputs. The drive’s analog
outputs can be:
• any parameter in
Group 01: OPERATING DATA
• limited to programmable minimum and maximum values of output current
• scaled (and/or inverted) by defining the minimum and maximum values of the
source parameter (or content). Defining an maximum value (parameter 1503 or
1509) that is less than the content minimum value (parameter 1502 or 1508)
results in an inverted output.
• filtered.
Code Description
1501
AO1 CONTENT SEL
Defines the content for analog output AO1.
99 =
EXCITE
PTC
– Provides a current source for sensor type PTC. Output = 1.6 mA. See
Group 35: MOTOR TEMP
MEAS
.
100 =
EXCITE
PT
100 – Provides a current source for sensor type PT100. Output = 9.1 mA. See
Group 35: MOTOR
TEMP MEAS
.
101…159 – Output corresponds to a parameter in
Group 01: OPERATING DATA
.
• Parameter defined by value (value 102 = parameter 0102)
1502
AO1 CONTENT MIN
Sets the minimum content value.
• Content is the parameter selected by parameter 1501.
• Minimum value refers to the minimum content value that will be
converted to an analog output.
• These parameters (content and current min. and max. settings)
provide scale and offset adjustment for the output. See the
figure.
1503
AO1 CONTENT MAX
Sets the maximum content value
• Content is the parameter selected by parameter 1501.
• Maximum value refers to the maximum content value that will
be converted to an analog output.
1504
MINIMUM AO1
Sets the minimum output current.
1505
MAXIMUM AO1
Sets the maximum output current.
1506
FILTER AO1
Defines the filter time constant for
AO
1.
• The filtered signal reaches 63% of a step change within the time
specified.
• See the figure in parameter 1303.
1507
AO2 CONTENT SEL
Defines the content for analog output
AO
2. See
AO
1
CONTENT
SEL
above.
1508
AO2 CONTENT MIN
Sets the minimum content value. See
AO
1
CONTENT
MIN
above.
1509
AO2 CONTENT MAX
Sets the maximum content value. See
AO
1
CONTENT
MAX
above.
1510
MINIMUM AO2
Sets the minimum output current. See
MINIMUM
AO
1 above.
AO (mA)
AO
CONTENT
P 1504 /
P 1502 / 1508
P 1503 / 1509
AO (mA)
AO
CONTENT
P 1505 /
P 1504 /
P 1503 / 1509
P 1502 / 1508
P 1505 /
P 1511
P 1510
P 1511
P 1510