ACS550-02/U2 User’s Manual
Embedded fieldbus
DCU profile
The following tables describe the
STATUS
WORD
content for the DCU profile.
DCU profile
STATUS
WORD
(See parameter 0303)
Bit
Name
Value
Status
0
READY
1
Drive is ready to receive start command.
0
Drive is not ready.
1
ENABLED
1
External run enable signal received.
0
No external run enable signal received.
2
STARTED
1
Drive has received start command.
0
Drive has not received start command.
3
RUNNING
1
Drive is modulating.
0
Drive is not modulating.
4
ZERO_SPEED
1
Drive is at zero speed.
0
Drive has not reached zero speed.
5 ACCELERATE
1
Drive is accelerating.
0
Drive is not accelerating.
6
DECELERATE
1
Drive is decelerating.
0
Drive is not decelerating.
7
AT_SETPOINT
1
Drive is at setpoint.
0
Drive has not reached setpoint.
8
LIMIT
1
Operation is limited. Reference cannot be followed.
0
Operation is not limited.
9
SUPERVISION
1
A supervised parameter (
Group 32: SUPERVISION
) is outside
its limits.
0
All supervised parameters are within limits.
10 REV_REF
1
Drive reference is in reverse direction.
0
Drive reference is in forward direction.
11
REV_ACT
1
Drive is running in reverse direction.
0
Drive is running in forward direction.
12 PANEL_LOCAL
1
Control is in control panel (or PC tool) local mode.
0
Control is not in control panel local mode.
13 FIELDBUS_LOCAL 1
Control is in fieldbus local mode (steals control panel local).
0
Control is not in fieldbus local mode.
14 EXT2_ACT
1
Control is in EXT2 mode.
0
Control is in EXT1 mode.
15 FAULT
1
Drive is in a fault state.
0
Drive is not in a fault state.