ACS550-02/U2 User’s Manual
Diagnostics
Faults that indicate conflicts in the parameter settings are listed below.
101…
199
SYSTEM
ERROR
Error internal to the drive. Contact your local ABB representative and report
the error number.
201…
299
SYSTEM
ERROR
Error in the system. Contact your local ABB representative and report the
error number.
-
UNKNOWN
DRIVE
TYPE
:
ACS550
SUPPORTED
DRIVES
:
X
Wrong type of panel, i.e. panel that supports drive X but not the ACS550,
has been connected to the ACS550.
Fault
code
Fault name in
panel
Description and recommended corrective action
1000
PAR
HZRPM
Parameter values are inconsistent. Check for any of the following:
• 2001
MINIMUM
SPEED
> 2002
MAXIMUM
SPEED
.
• 2007
MINIMUM
FREQ
> 2008
MAXIMUM
FREQ
.
• 2001
MINIMUM
SPEED
/ 9908
MOTOR
NOM
SPEED
is outside proper range
(> 50).
• 2002
MAXIMUM
SPEED
/ 9908
MOTOR
NOM
SPEED
is outside proper range
(> 50).
• 2007
MINIMUM
FREQ
/ 9907
MOTOR
NOM
FREQ
is outside proper range
(> 50).
• 2008
MAXIMUM
FREQ
/ 9907
MOTOR
NOM
FREQ
is outside proper range
(> 50).
1001
PAR
PFC
REF
NEG
Parameter values are inconsistent. Check for the following:
• 2007
MINIMUM
FREQ
is negative, when 8123
PFC
ENABLE
is active.
1002
RESERVED
Not used.
1003
PAR
AI
SCALE
Parameter values are inconsistent. Check for any of the following:
• 1301
MINIMUM
AI
1 > 1302
MAXIMUM
AI
1.
• 1304
MINIMUM
AI
2 > 1305
MAXIMUM
AI
2.
1004
PAR
AO
SCALE
Parameter values are inconsistent. Check for any of the following:
• 1504
MINIMUM
AO
1 > 1505
MAXIMUM
AO
1.
• 1510
MINIMUM
AO
2 > 1511
MAXIMUM
AO
2.
1005
PAR
PCU
2
Parameter values for power control are inconsistent: Improper motor
nominal kVA or motor nominal power. Check for the following:
• 1.1 < (9906
MOTOR
NOM
CURR
· 9905
MOTOR
NOM
VOLT
· 1.73 /
P
N
) < 3.0
where:
P
N
= 1000 · 9909
MOTOR
NOM
POWER
(if units are kW)
or
P
N
= 746 · 9909
MOTOR
NOM
POWER
(if units are hp, e.g. in US)
1006
PAR
EXT
RO
Parameter values are inconsistent. Check for the following:
• Extension relay module not connected and
• 1410…1412
RELAY
OUTPUTS
4…6 have non-zero values.
1007
PAR
FIELDBUS
MISSING
Parameter values are inconsistent. Check for and correct:
• A parameter is set for fieldbus control (e.g. 1001
EXT
1
COMMANDS
= 10
(
COMM
)), but 9802
COMM
PROT
SEL
= 0.
1008
PAR
PFC
MODE
Parameter values are inconsistent – 9904
MOTOR
CTRL
MODE
must be = 3
(
SCALAR
:
FREQ
), when 8123
PFC
ENABLE
is activated.
Fault
code
Fault name in
panel
Description and recommended corrective action