background image

Note!

  

This guide does not provide detailed installation,    

 

safety or operation instructions. See the ACS550    

 

User’s Manual for complete information.

Prepare for Installation

 

Warning!

 The ACS550 should ONLY be installed    

  by a qualified electrician.

Unpack the Drive

Note!

  

Lift ACS550 by its chassis and not by its cover.

1. Unpack the drive.

2. Check for any damage.

3. Check the contents against the order / shipping label. 

Check

Motor compatibility

 - Motor type, nominal current, 

frequency, and voltage range must match drive specifications.

Suitable environment 

- Drive requires heated, indoor 

controlled environment that is suitable for the selected 

enclosure.

Wiring

 - Follow local codes for wiring, circuit protection, and 

EMC requirements.

Refer to User’s Manual and confirm that all preparations are 

complete.

Tools Required

Screwdrivers, wire stripper, tape measure, mounting screws 

or bolts, and drill.

Collect Motor Data

Collect the following motor data from the motor nameplate for 

later use in the ACS550 startup:

Drive Identification

Use the following chart to interpret the type code found on the 

drive label.

Prepare the Mounting Location

The drive requires a smooth, vertical, solid 

surface, free from heat and moisture, with 

free space for air flow - 200 mm (8 in) above 

and below, and 25 mm (1 in) around the 

sides of the drive.

1. Mark the mounting points.

2. Drill the mounting holes.

Remove the Front Cover

1. Remove the control panel, if attached.

2. Loosen the captive screw at the top.

3. Pull near the top to remove the cover.

Mount the Drive

Note!

 

Lift the ACS550 by its metal chassis.

1. Position the ACS550 onto the mounting screws or bolts and 

securely tighten in all four corners.

2. Non-English speaking locations: Attach a warning sticker in 

the appropriate language over the existing warning on the top 
of the module.

Install the Wiring

Note!

 

Use separate conduit runs for input power, motor    

 

and control wiring.

Wiring power

1. Open the appropriate knockouts in 

the gland box.

2. Install the cable clamps for the 

power/motor cables.

3. On the input power cable, strip the 

sheathing back far enough to route individual wires.

4. On the motor cable, strip the 

sheathing back far enough to expose 

the copper wire screen so that the 

screen can be twisted into a pig-tail. 

Keep the pig-tail short to minimize 

noise radiation. - 360° grounding 

under the clamp is recommended for 

the motor cable to minimize noise 

radiation. In this case, remove the 

sheathing at the cable clamp.

5. Route both cables through the clamps.

6. Connect the pig-tail created from the motor cable screen to 

the GND terminal.

7. Strip and connect the power/motor wires, and the power 

ground wire to the drive terminals. See 

diagrams below, or Power connections 

in User’s Manual.

8. Install conduit/gland box and tighten 

the cable clamps.

 

 

Warning!

  For IT systems and corner grounded    

  TN systems, disconnect the internal EMC filter by  

 

  removing screws: EM1 and EM3 (frame sizes 

 

  R1-R4), or F1 and F2 (frame sizes R5-R6).

3AUA0000001558 REVF

Effective: 10/01/2007

Supersedes: 10/30/2006

Drive

IT

 Low Voltage AC Drives

Quick Start Guide

ACS550-U1 Drives (1 to 200 Hp) 

UL Type 1 / NEMA 1 / IP21

Overview

The installation of the ACS550 adjustable speed AC drive fol-

lows the outline below.

Application

This guide provides a quick reference for installing  

ACS550-U1 drives having a standard UL Type 1 (NEMA 1) 

enclosure.

 

 

                          ACS550 - U1 - 08A8 - 4 + ...

AC, Standard Drive - 550 series

Construction (region specific)

01 = Setup / parts for IEC install./compliance

U1 = Setup / parts for US install./compliance

Output current rating

See Ratings in User’s Manual for details

Voltage rating

 2 = 208 ... 240 VAC

 4 = 380 ... 480 VAC

 6 = 500 ... 600 VAC

Enclosure protection class/Options

No specification = IP 21 / UL Type 1 / NEMA 1

B055 = IP 54 / UL Type 12 / NEMA 12

ACS550-U1-08A8-4

U1 

 

3~380...480V    

I2N / I2hd

   8.8/6.9 A

PN/Phd

    5/3 Hp 

      S/N       *2030700001*