Supplemental Installation Manual for ACS580-0P
15
ACS580-0P
Power connection terminals
The following tables show maximum wire size and required tightening torque for
incoming power, grounding and motor terminals.
208/230 Volt
Output Ratings
Base
Drive
Frame
Size
Maximum Power Wiring Data
Type Code
1
A
HP
Circuit
Breaker
(+F255)
UL
(NEMA)
Type 1
and 12
Circuit
Breaker
UL
(NEMA)
Type 3R
2
Disconne
ct Switch
UL
(NEMA)
Type 1
and 12
Disconne
ct Switch
UL
(NEMA)
Type 3R
2
Motor
Terminals
Ground
Lugs UL
(NEMA)
Type 1
and 12
ACS580-0P-04A6-2
4.6
1
R1
#10
62 in-lbs
#10
62 in-lbs
#10
55 in-lbs
#10
55 in-lbs
#10
0.7 ft-lbs
#2
50 in-lbs
ACS580-0P-06A6-2
6.6
1.5
R1
ACS580-0P-07A5-2
7.5
2
R1
ACS580-0P-10A6-2
10.6
3
R1
ACS580-0P-017A-2
16.7
5
R1
#6
62 in-lbs
#6
62 in-lbs
#6
55 in-lbs
#6
55 in-lbs
ACS580-0P-024A-2
24.2
7.5
R2
#6
1.1 ft-lbs
ACS580-0P-031A-2
30.8
10
R2
#4
62 in-lbs
#4
62 in-lbs
#4
55 in-lbs
#4
55 in-lbs
ACS580-0P-046A-2
46.2
15
R3
#2
62 in-lbs
#2
62 in-lbs
#2
55 in-lbs
#2
55 in-lbs
#2
2.6 ft-lbs
ACS580-0P-059A-2
59.4
20
R3
#1
62 in-lbs
#1
62 in-lbs
#1
55 in-lbs
#1
55 in-lbs
ACS580-0P-075A-2
74.8
25
R4
#1/0
62 in-lbs
#1/0
62 in-lbs
#1/0
55 in-lbs
#1/0
55 in-lbs
#1
3.0 ft-lbs
ACS580-0P-088A-2
88
30
R5
#2/0
124 in-lbs
Consult
Factory
#2/0
275 in-lbs
Consult
Factory
#2/0
4.1 ft-lbs
#1/0
50 in-lbs
ACS580-0P-114A-2
114
40
R5
#1/0
124 in-lbs
#4/0
275 in-lbs
ACS580-0P-143A-2
143
50
R6
#3/0
124 in-lbs
200 MCM
275 in-lbs
300 MCM
22.1 ft-lbs
ACS580-0P-169A-2
169
60
R7
#4/0 124
in-lbs
500 MCM
29.5 ft-lbs
ACS580-0P-211A-2
211
75
R7
2 x 500
MCM
274 in-lbs
2 x 500
MCM
274 in-lbs
ACS580-0P-273A-2
273
100
R8
2 x 500
MCM
274 in-lbs
2 x 300
MCM
29.6 ft-lbs
1)
0P represents a disconnect with fuses. 0P+F255 represents a circuit breaker.
2)
Only available for packaged drives in box enclosures.
Summary of Contents for ACS580-0P
Page 2: ......
Page 12: ...12 Supplemental Installation Manual for ACS580 0P ACS580 0P ...
Page 14: ...14 Supplemental Installation Manual for ACS580 0P ACS580 0P ...
Page 22: ...22 Supplemental Installation Manual for ACS580 0P ACS580 0P Dimensions Px1 1 R1 Type 1 ...
Page 23: ...Supplemental Installation Manual for ACS580 0P 23 ACS580 0P Px1 12 R1 Type 12 ...
Page 24: ...24 Supplemental Installation Manual for ACS580 0P ACS580 0P Px1 2 R2 Type 1 ...
Page 25: ...Supplemental Installation Manual for ACS580 0P 25 ACS580 0P Px12 2 R2 Type 12 ...
Page 26: ...26 Supplemental Installation Manual for ACS580 0P ACS580 0P Px1 3 R3 Type 1 ...
Page 27: ...Supplemental Installation Manual for ACS580 0P 27 ACS580 0P Px12 3 R3 Type 12 ...
Page 28: ...28 Supplemental Installation Manual for ACS580 0P ACS580 0P Px1 4 R4 Type 1 ...
Page 29: ...Supplemental Installation Manual for ACS580 0P 29 ACS580 0P Px12 4 R4 Type 12 ...
Page 30: ...30 Supplemental Installation Manual for ACS580 0P ACS580 0P PxB3R 1 R1 R2 Type 3R ...
Page 31: ...Supplemental Installation Manual for ACS580 0P 31 ACS580 0P PxB3R 2 R3 R4 Type 3R ...
Page 32: ...32 Supplemental Installation Manual for ACS580 0P ACS580 0P PxB1 3 R5 R8 Type 1 ...
Page 33: ...Supplemental Installation Manual for ACS580 0P 33 ACS580 0P PxB12 3 R5 R8 Type 12 ...
Page 34: ...34 Supplemental Installation Manual for ACS580 0P ACS580 0P Page intentionally left blank ...
Page 35: ......