Supplemental Installation Manual for ACS580-0P
17
ACS580-0P
Branch circuit protection
Input power is connected to the ACS580 through a door interlocked disconnect
switch or circuit breaker. When connected to a 240V or 480V power source, the
ACS580 with the circuit breaker option is suitable for use on a circuit capable of
delivering not more than 100,000 RMS symmetrical amperes. When connected to a
600V power source, F255 configurations are suitable for use on a circuit capable of
delivering not more than 10,000 RMS symmetrical amperes (75-150 HP), and not
more than 25,000 RMS symmetrical amperes (2-60 HP).
Fuses
Note:
The UL listed drive fuses in the table are provided in the purchased product.
• Replacement fuses are required to be of the same class, current rating, and
voltage rating. Fuses from other manufacturers can be used if they are 600V rated
and meet the specifications given in the table.
• Fuses with higher current rating than specified must not be used.
575 Volt
Output Ratings
Base
Drive
Frame
Size
Maximum Power Wiring Data
Type Code
1, 2
A
HP
Circuit
Breaker
(+F255)
UL
(NEMA)
Type 1
and 12
Circuit
Breaker
UL
(NEMA)
Type 3R
4
Disconne
ct Switch
UL
(NEMA)
Type 1
and 12
Disconne
ct Switch
UL
(NEMA)
Type 3R
4
Motor
Terminals
Ground
Lugs UL
(NEMA)
Type 1
and 12
ACS580-0P-02A7-6
2.7
2
R2
#10
62 in-lbs
#10
62 in-lbs
#10
55 in-lbs
#10
55 in-lbs
#6
1.1 ft-lbs
#2
50 in-lbs
ACS580-0P-03A9-6
3.9
3
R2
#12
62 in-lbs
#12
62 in-lbs
ACS580-0P-06A1-6
6.1
5
R2
#10
62 in-lbs
#10
62 in-lbs
ACS580-0P-09A0-6
9
7.5
R2
ACS580-0P-011A-6
11
10
R2
ACS580-0P-017A-6
17
15
R2
#6
62 in-lbs
#6
62 in-lbs
#6
55 in-lbs
#6
55 in-lbs
ACS580-0P-022A-6
22
20
R3
#2
2.6 ft-lbs
ACS580-0P-027A-6
27
25
R3
#4
62 in-lbs
#4
62 in-lbs
#4
55 in-lbs
#4
55 in-lbs
ACS580-0P-032A-6
32
30
R3
ACS580-0P-041A-6
41
40
R5
#3
62 in-lbs
Consult
Factory
#3
55 in-lbs
Consult
Factory
#2/0
4.1 ft-lbs
ACS580-0P-052A-6
3
52
50
R5
#2
62 in-lbs
#2
55 in-lbs
ACS580-0P-062A-6
62
60
R6
#1
62 in-lbs
#1
275 in-lbs
300 MCM
29.5 ft-lbs
ACS580-0P-077A-6
77
75
R6
#1/0
62 in-lbs
#1/0
275 in-lbs
3 x #3/0
250 in-lbs
ACS580-0P-099A-6
99
100
R7
#3/0
124 in-lbs
#3/0
275 in-lbs
500 MCM
29.5 ft.lbs
ACS580-0P-125A-6
125
125
R7
250 MCM
124 in-lbs
250 MCM
275 in-lbs
ACS580-0P-144A-6
144
150
R8
300 MCM
275 in-lbs
2 x 300
MCM
29.6 ft-lbs
1)
“0P” represents a disconnect with fuses. 0P+F255 represents a circuit breaker.
2)
0P+F255 is rated 600Y/347V unless otherwise specified. For use on solidly grounded Wye source only.
3)
0P+F255 supports Delta network configuration.
4)
Only available for packaged drives in box enclosures.
Summary of Contents for ACS580-0P
Page 2: ......
Page 12: ...12 Supplemental Installation Manual for ACS580 0P ACS580 0P ...
Page 14: ...14 Supplemental Installation Manual for ACS580 0P ACS580 0P ...
Page 22: ...22 Supplemental Installation Manual for ACS580 0P ACS580 0P Dimensions Px1 1 R1 Type 1 ...
Page 23: ...Supplemental Installation Manual for ACS580 0P 23 ACS580 0P Px1 12 R1 Type 12 ...
Page 24: ...24 Supplemental Installation Manual for ACS580 0P ACS580 0P Px1 2 R2 Type 1 ...
Page 25: ...Supplemental Installation Manual for ACS580 0P 25 ACS580 0P Px12 2 R2 Type 12 ...
Page 26: ...26 Supplemental Installation Manual for ACS580 0P ACS580 0P Px1 3 R3 Type 1 ...
Page 27: ...Supplemental Installation Manual for ACS580 0P 27 ACS580 0P Px12 3 R3 Type 12 ...
Page 28: ...28 Supplemental Installation Manual for ACS580 0P ACS580 0P Px1 4 R4 Type 1 ...
Page 29: ...Supplemental Installation Manual for ACS580 0P 29 ACS580 0P Px12 4 R4 Type 12 ...
Page 30: ...30 Supplemental Installation Manual for ACS580 0P ACS580 0P PxB3R 1 R1 R2 Type 3R ...
Page 31: ...Supplemental Installation Manual for ACS580 0P 31 ACS580 0P PxB3R 2 R3 R4 Type 3R ...
Page 32: ...32 Supplemental Installation Manual for ACS580 0P ACS580 0P PxB1 3 R5 R8 Type 1 ...
Page 33: ...Supplemental Installation Manual for ACS580 0P 33 ACS580 0P PxB12 3 R5 R8 Type 12 ...
Page 34: ...34 Supplemental Installation Manual for ACS580 0P ACS580 0P Page intentionally left blank ...
Page 35: ......