18
Supplemental Installation Manual for ACS580-0P
ACS580-0P
208 Volt fuses for packaged drive
460 Volt fuses for packaged drive
208 Volt
Nominal Output
Range
Base
Drive
Frame
Size
Internal Drive Fuse
Rating
External Fuse for Disconnect
Option
Type code
1
Drive
current
Package
power
A
HP
Class
Current
rating
Class
Max current
rating
ACS580-0P-04A6-2
4.6
1
R1
Class CC
15A
N/A
N/A
ACS580-0P-06A6-2
6.6
1.5
R1
Class CC
15A
N/A
N/A
ACS580-0P-07A5-2
7.5
2
R1
Class CC
15A
N/A
N/A
ACS580-0P-10A6-2
10.6
3
R1
Class CC
15A
N/A
N/A
ACS580-0P-017A-2
16.7
5
R1
Class CC
30A
N/A
N/A
ACS580-0P-024A-2
24.2
7.5
R2
Class CC
30A
N/A
N/A
ACS580-0P-031A-2
30.8
10
R2
Class T
40A
N/A
N/A
ACS580-0P-046A-2
46.2
15
R3
Class T
80A
N/A
N/A
ACS580-0P-059A-2
59.4
20
R3
Class T
80A
N/A
N/A
ACS580-0P-075A-2
74.8
25
R4
Class T
100A
N/A
N/A
ACS580-0P-088A-2
88
30
R5
Class T
110A
N/A
N/A
ACS580-0P-114A-2
114
40
R5
Class T
150A
N/A
N/A
ACS580-0P-143A-2
143
50
R6
Class T
200A
N/A
N/A
ACS580-0P-169A-2
169
60
R7
Class T
250A
N/A
N/A
ACS580-0P-211A-2
211
75
R7
Class T
300A
Class J or RK1
400A
ACS580-0P-273A-2
273
100
R8
Class T
350A
Class J or RK1
400A
1)
“0P” represents a disconnect and 0P+F255 represents a circuit breaker
480 Volt
Nominal Output
Range
Base
Drive
Frame
Size
Internal Drive Fuse
Rating
External Fuse for Disconnect
Option
Type code
1
Drive
current
Package
power
A
HP
Class
Current
rating
Class
Max current
rating
ACS580-0P-02A1-4
2.1
1
R1
Class CC
15A
N/A
N/A
ACS580-0P-03A0-4
3
1.5
R1
Class CC
15A
N/A
N/A
ACS580-0P-03A5-4
3.5
2
R1
Class CC
15A
N/A
N/A
ACS580-0P-04A8-4
4.8
3
R1
Class CC
15A
N/A
N/A
ACS580-0P-07A6-4
7.6
5
R1
Class CC
15A
N/A
N/A
ACS580-0P-012A-4
12
7.5
R1
Class CC
15A
N/A
N/A
ACS580-0P-014A-4
14
10
R2
Class CC
30A
N/A
N/A
ACS580-0P-023A-4
23
15
R2
Class CC
30A
N/A
N/A
ACS580-0P-027A-4
27
20
R3
Class T
40A
N/A
N/A
ACS580-0P-034A-4
34
25
R3
Class T
60A
N/A
N/A
ACS580-0P-044A-4
44
30
R3
Class T
60A
N/A
N/A
ACS580-0P-052A-4
52
40
R4
Class T
80A
N/A
N/A
ACS580-0P-065A-4
65
50
R4
Class T
90A
N/A
N/A
ACS580-0P-077A-4
77
60
R4
Class T
100A
N/A
N/A
ACS580-0P-096A-4
96
75
R5
Class T
150A
N/A
N/A
ACS580-0P-124A-4
124
100
R6
Class T
200A
N/A
N/A
ACS580-0P-156A-4
156
125
R7
Class T
225A
N/A
N/A
ACS580-0P-180A-4
180
150
R7
Class T
300A
N/A
N/A
ACS580-0P-240A-4
240
200
R8
Class T
350A
Class J or RK1
400A Max
1)
“0P” represents a disconnect and 0P+F255 represents a circuit breaker
Summary of Contents for ACS580-0P
Page 2: ......
Page 12: ...12 Supplemental Installation Manual for ACS580 0P ACS580 0P ...
Page 14: ...14 Supplemental Installation Manual for ACS580 0P ACS580 0P ...
Page 22: ...22 Supplemental Installation Manual for ACS580 0P ACS580 0P Dimensions Px1 1 R1 Type 1 ...
Page 23: ...Supplemental Installation Manual for ACS580 0P 23 ACS580 0P Px1 12 R1 Type 12 ...
Page 24: ...24 Supplemental Installation Manual for ACS580 0P ACS580 0P Px1 2 R2 Type 1 ...
Page 25: ...Supplemental Installation Manual for ACS580 0P 25 ACS580 0P Px12 2 R2 Type 12 ...
Page 26: ...26 Supplemental Installation Manual for ACS580 0P ACS580 0P Px1 3 R3 Type 1 ...
Page 27: ...Supplemental Installation Manual for ACS580 0P 27 ACS580 0P Px12 3 R3 Type 12 ...
Page 28: ...28 Supplemental Installation Manual for ACS580 0P ACS580 0P Px1 4 R4 Type 1 ...
Page 29: ...Supplemental Installation Manual for ACS580 0P 29 ACS580 0P Px12 4 R4 Type 12 ...
Page 30: ...30 Supplemental Installation Manual for ACS580 0P ACS580 0P PxB3R 1 R1 R2 Type 3R ...
Page 31: ...Supplemental Installation Manual for ACS580 0P 31 ACS580 0P PxB3R 2 R3 R4 Type 3R ...
Page 32: ...32 Supplemental Installation Manual for ACS580 0P ACS580 0P PxB1 3 R5 R8 Type 1 ...
Page 33: ...Supplemental Installation Manual for ACS580 0P 33 ACS580 0P PxB12 3 R5 R8 Type 12 ...
Page 34: ...34 Supplemental Installation Manual for ACS580 0P ACS580 0P Page intentionally left blank ...
Page 35: ......