Make sure that …
The insulation resistance of the input power cable, motor cable and motor is meas-
ured according to local regulations and the manuals of the drive.
The drive is attached securely on an even, vertical and non-flammable wall.
The cooling air can flow freely in and out of the drive.
If the drive is connected to a network other than a symmetrically grounded TN-S
system: You have done all the required modifications (for example, you may need
to disconnect the EMC filter or ground-to-phase varistor). See the electrical installa-
tion instructions.
Appropriate AC fuses and main disconnecting device are installed.
There is an adequately sized protective earth (ground) conductor(s) between the
drive and the switchboard, the conductor is connected to correct terminal, and the
terminal is tightened to the correct torque.
Grounding has also been measured according to the regulations.
The input power cable is connected to the correct terminals, the phase order is
correct, and the terminals are tightened to the correct torque.
There is an adequately sized protective earth (ground) conductor between the motor
and the drive. The conductor is connected to the correct terminal, and the terminal
is tightened to the correct torque.
Grounding has also been measured according to the regulations.
The motor cable is connected to the correct terminals, the phase order is correct,
and the terminals are tightened to the correct torque.
The motor cable is routed away from other cables.
No power factor compensation capacitors are connected to the motor cable.
If an external brake resistor is connected to the drive: There is an adequately sized
protective earth (ground) conductor between the brake resistor and the drive, and
the conductor is connected to the correct terminal, and the terminals are tightened
to the correct torque. Grounding has also been measured according to the regula-
tions.
If an external brake resistor is connected to the drive: The brake resistor cable is
connected to the correct terminals, and the terminals are tightened to the correct
torque.
If an external brake resistor is connected to the drive: The brake resistor cable is
routed away from other cables.
238 Installation checklist
Summary of Contents for ACS580 Series
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS580 01 drives Hardware manual...
Page 2: ......
Page 4: ......
Page 19: ...Further information Table of contents 19...
Page 20: ...20...
Page 34: ...34...
Page 58: ...58...
Page 128: ...128...
Page 163: ...R5 4 6 11 11 10 4 3 5 7 8 9 0 5 0 6 N m 0 4 lbf ft 8 4 Electrical installation Global IEC 163...
Page 207: ...R6 R9 11 11 7 3 9 5 10 6 4 R6 R9 0 4 lbf ft Electrical installation North America 207...
Page 214: ...214...
Page 236: ...236...
Page 240: ...240...
Page 242: ...242...
Page 258: ...3a 3b 3c 4 5 7 6 2d 2a 2b 2c 258 Maintenance...
Page 364: ...Frame R1 IP21 UL Type 1 3AXD10000601652 364 Dimension drawings...
Page 365: ...Frame R1 IP55 UL Type 12 3AXD10000601699 Dimension drawings 365...
Page 366: ...Frame R1 IP55 F278 UL Type 12 366 Dimension drawings...
Page 367: ...Frame R1 IP66 UL Type 4X B066 3AXD50001012694 Dimension drawings 367...
Page 368: ...Frame R1 IP66 UL Type 4X B063 3AXD50001012694 368 Dimension drawings...
Page 369: ...Frame R1 IP66 UL Type 4X C193 3AXD50001012694 Dimension drawings 369...
Page 370: ...Frame R2 IP21 UL Type 1 3AXD10000602398 370 Dimension drawings...
Page 371: ...Frame R2 IP55 UL Type 12 3AXD10000602401 Dimension drawings 371...
Page 372: ...Frame R2 IP55 F278 UL Type 12 372 Dimension drawings...
Page 373: ...Frame R2 IP66 UL Type 4X B066 3AXD50000999286 Dimension drawings 373...
Page 374: ...Frame R2 IP66 UL Type 4X B063 3AXD50000999286 374 Dimension drawings...
Page 375: ...Frame R2 IP66 UL Type 4X C193 3AXD50000999286 Dimension drawings 375...
Page 376: ...Frame R3 IP21 UL Type 1 3AXD10000602466 376 Dimension drawings...
Page 377: ...Frame R3 IP55 UL Type 12 3AXD10000602519 Dimension drawings 377...
Page 378: ...Frame R3 IP55 E223 UL Type 12 378 Dimension drawings...
Page 379: ...Frame R3 IP55 F278 F316 UL Type 12 Dimension drawings 379...
Page 380: ...Frame R3 IP66 UL Type 4X B066 3AXD50001013059 380 Dimension drawings...
Page 381: ...Frame R3 IP66 UL Type 4X B063 3AXD50001013059 Dimension drawings 381...
Page 382: ...Frame R3 IP66 UL Type 4X C193 3AXD50001013059 382 Dimension drawings...
Page 383: ...Frame R4 IP21 UL Type 1 3AXD10001330082 Dimension drawings 383...
Page 384: ...Frame R4 IP55 UL Type 12 3AXD10001330271 384 Dimension drawings...
Page 385: ...Frame R4 IP55 E223 UL Type 12 3AXD10001373680 Dimension drawings 385...
Page 386: ...Frame R4 IP55 F278 F316 UL Type 12 3AXD10001373680 386 Dimension drawings...
Page 387: ...Frame R5 IP21 UL Type 1 3AXD10000427933 Dimension drawings 387...
Page 388: ...Frame R5 IP55 UL Type 12 3AXD10000386017 388 Dimension drawings...
Page 389: ...Frame R5 IP55 E223 UL Type 12 Dimension drawings 389...
Page 390: ...Frame R5 IP55 F278 F316 UL Type 12 390 Dimension drawings...
Page 391: ...Frame R6 IP21 UL Type 1 3AXD10000258705 Dimension drawings 391...
Page 392: ...Frame R6 IP55 UL Type 12 3AXD10000330667 392 Dimension drawings...
Page 393: ...Frame R7 IP21 UL Type 1 3AXD10000258995 Dimension drawings 393...
Page 394: ...Frame R7 IP55 UL Type 12 3AXD10000330932 394 Dimension drawings...
Page 395: ...Frame R8 IP21 UL Type 1 3AXD10000287670 Dimension drawings 395...
Page 396: ...Frame R8 IP55 UL Type 12 3AXD10000332446 396 Dimension drawings...
Page 397: ...Frame R9 IP21 UL Type 1 3AXD10000287428 Dimension drawings 397...
Page 398: ...Frame R9 IP55 UL Type 12 3AXD10000334310 398 Dimension drawings...
Page 459: ...Optional I O extension and adapter modules 459...
Page 460: ...460...