Internal cooling circuit
141
Specifications
Temperature limits
Ambient temperature:
See chapter
.
Minimum coolant inlet temperature:
Condensation is not allowed. The minimum
coolant temperature to avoid condensation (at an atmospheric pressure of 1 bar) is
shown below as a function of the relative humidity (
φ
) and the ambient
temperature (
T
air
).
Maximum coolant inlet temperature for the drive
Drive with the optional liquid cooling unit (+C140 or +C141):
• 38 °C when the drive output capacity is not derated
• 38 °C … 45 °C when the drive output capacity is derated by 1% per 1 °C
temperature increase.
Drive without the optional liquid cooling unit:
• 42 °C when the drive output capacity is not derated
• 42 °C … 48 °C when the drive output capacity is derated by 1% per 1 °C
temperature increase.
Maximum inlet temperature variation:
±4°C
Maximum temperature rise:
13 °C; depends on mass flow.
Pressure limits
Base pressure:
100…150 kPa (recommended); 200 kPa (maximum). “Base
pressure” denotes the pressure of the system compared with the atmospheric
pressure when the cooling circuit is filled with coolant.
T
air
(°C)
Min.
T
coolant
(°C)
φ
= 95%
φ
= 80%
φ
= 65%
φ
= 50%
φ
= 40%
5
4.3
1.9
-0.9
-4.5
-7.4
10
9.2
6.7
3.7
-0.1
-3.0
15
14.2
11.5
8.4
4.6
1.5
20
19.2
16.5
13.2
9.4
6.0
25
24.1
21.4
17.9
13.8
10.5
30
29.1
26.2
22.7
18.4
15.0
35
34.1
31.1
27.4
23.0
19.4
40
39.0
35.9
32.2
27.6
23.8
45
44.0
40.8
36.8
32.1
28.2
50
49.0
45.6
41.6
36.7
32.8
55
53.9
50.4
46.3
42.2
37.1
Not allowed as standard but the coolant temperature must be 5 °C or
above. Consult an ABB representative if operation below coolant
temperature 5 °C is required.
Example:
At an air temperature of 45 °C and relative humidity of 65% the coolant
temperature may not be below +36.8 °C
Summary of Contents for ACS800-17LC
Page 1: ...ABB industrial drives Hardware manual ACS800 17LC Drives 55 to 5200 kW ...
Page 4: ......
Page 10: ...Update notice 6 ...
Page 18: ...Table of contents 12 ...
Page 26: ...Safety instructions 20 ...
Page 32: ...Introduction to the manual 26 ...
Page 60: ...Hardware description 54 ...
Page 74: ...Mechanical installation 68 ...
Page 114: ...Electrical installation 108 ...
Page 142: ...Maintenance 136 ...
Page 150: ...Internal cooling circuit 144 ...
Page 179: ...Dimensions 173 Frame sizes R7i R7i and R8i R8i bottom entry exit ...
Page 180: ...Dimensions 174 Frame sizes R7i R7i and R8i R8i marine units C121 ...
Page 182: ...www abb com drives www abb com drivespartners Contact us 3AUA0000065339 Rev B EN 2016 06 07 ...