Technical data
120
Quick guide for selecting between gG and aR fuses
The table below is a short cut in selecting between gG and aR fuses. The
combinations (cable size, cable length, transformer size and fuse type) in the table
fulfil the minimum requirements for the proper operation of the fuse.
Note 1:
The supply transformer minimum power in kVA is calculated with a z
k
value of 6% and
frequency 50 Hz.
Note 2:
The table is not intended for transformer selection - that must be done separately.
The following parameters can effect on the correct operation of the protection:
ACS800-07 size
Cable type
Supply transformer minimum apparent power
S
N
(kVA)
Copper
Aluminium
Maximum cable length with gG fuses
Maximum cable length with aR fuses
10 m
50 m
100 m
10 m
100 m
200 m
Three-phase supply voltage 380 V,
400 V
or 415 V
-0075-3
3×70 Cu
3×95 Al
130
140
160
99
99
140
-0100-3
3×95 Cu
3×120 Al
150
160
190
120
120
140
-0120-3
3×120 Cu
3×185 Al
170
190
210
140
140
140
-0130-3
3×150 Cu
3×240 Al
200
220
250
160
160
160
-0165-3
3×185 Cu
3×240 Al
240
260
310
180
180
200
-0205-3
3×240 Cu
2 × (3x120) Al
240
260
310
200
200
200
-0260-3
3 × (3×70) Cu
3 × (3×120) Al
430
460
560
310
310
310
-0320-3
3 × (3×95) Cu
2 × (3×240) Al
530
600
750
350
350
440
-0400-3
3 × (3×120) Cu 3 × (3×185) Al
530
600
750
410
470
660
-0440-3
3 × (3×150) Cu 3 × (3×240) Al
700
770
930
470
530
730
-0490-3
3 × (3×150) Cu 3 × (3×240) Al
700
770
930
490
530
730
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or
500
V
-0105-5
3×70 Cu
3×95 Al
160
170
190
130
130
150
-0120-5
3×95 Cu
3×120 Al
190
200
220
140
140
150
-0140-5
3×95 Cu
3×150 Al
190
200
220
160
160
160
-0150-5
3×120 Cu
3×185 Al
220
230
250
180
180
180
-0165-5
3x150 Cu
3x240 Al
250
260
290
200
200
200
-0205-5
3×185 Cu
3×240 Al
290
320
360
230
230
230
-0255-5
3×240 Cu
2 × (3×120) Al
290
320
360
250
250
250
-0320-5
2 × (3×120) Cu 3 × (3×95) Al
530
570
670
370
370
370
-0400-5
2 × (3×150) Cu 2 × (3×240) Al
660
720
840
440
440
480
-0440-5
3 × (3×95) Cu
3 × (3×150) Al
660
720
840
500
570
760
-0490-5
3 × (3×120) Cu 3 × (3×185) Al
660
720
840
520
570
760
-0550-5
2 × (3×240) Cu 3 × (3×240) Al
880
980
1200
580
670
880
-0610-5
3 × (3×150) Cu 3 × (3×240) Al
880
980
1200
610
670
880
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or
690
V
-0070-7
3×25 Cu
3×50 Al
95
95
99
95
95
95
-0100-7
3×35 Cu
3×50 Al
130
140
150
110
110
110
-0120-7
3×50 Cu
3×70 Al
180
180
190
140
140
140
-0145-7
3×70 Cu
3×95 Al
220
220
240
160
160
160
-0175-7
3×95 Cu
3×120 Al
260
260
280
200
200
200
-0205-7
3×95 Cu
3×150 Al
340
360
390
230
230
230
-0260-7
3×150 Cu
3×185 Al
340
360
390
260
260
260
-0320-7
3×240 Cu
2 × (3×120) Al
400
410
430
360
360
360
-0400-7
3×240 Cu
3 × (3×70) Al
550
570
610
400
400
400
-0440-7
2 × (3×120) Cu 2 × (3×150) Al
730
780
860
460
460
460
-0490-7
2 × (3×120) Cu 3 × (3×95) Al
730
780
860
510
510
510
-0550-7
2 × (3×150) Cu 3 × (3×120) Al
730
780
860
560
560
560
-0610-7
3 × (3×95) Cu
3 × (3×150) Al
960
1000
1100
640
640
640
00556489
Summary of Contents for ACS800-U7
Page 1: ...ACS800 Hardware Manual ACS800 07 Drives 45 to 560 kW ACS800 U7 Drives 50 to 600 hp ...
Page 4: ......
Page 28: ...Operation principle and hardware description 28 ...
Page 51: ...Planning the electrical installation 51 ...
Page 60: ...Planning the electrical installation 60 ...
Page 76: ...Electrical installation 76 ...
Page 84: ...Motor control and I O board RMIO 84 ...
Page 112: ...Maintenance 112 ...
Page 138: ...Dimensional drawings 138 Frame sizes R5 and R6 64778340_1 5 K ...
Page 139: ...Dimensional drawings 139 Frame sizes R7 and R8 68749930_1 7 C ...
Page 140: ...Dimensional drawings 140 IP54 and IP54R units of frame sizes R7 and R8 68749930_6 6 C ...
Page 148: ...3AFE64702165 Rev H EN 2012 09 19 Contact us www abb com drives www abb com drivespartners ...