Planning the electrical installation
55
2. If capacitor load is increased/decreased step by step when the AC drive is
connected to the power line: Ensure that the connection steps are low enough not
to cause voltage transients that would trip the drive.
3. Check that the power factor compensation unit is suitable for use in systems with
AC drives, that is, harmonic generating loads. In such systems, the compensation
unit should typically be equipped with a blocking reactor or harmonic filter.
Equipment connected to the motor cable
Installation of safety switches, contactors, connection boxes, etc.
To minimize the emission level when safety switches, contactors, connection boxes
or similar equipment are installed in the motor cable between the drive and the
motor:
• EU: Install the equipment in a metal enclosure with 360 degrees grounding for the
shields of both the incoming and outgoing cable, or connect the shields of the
cables otherwise together.
• US: Install the equipment in a metal enclosure in a way that the conduit or motor
cable shielding runs consistently without breaks from the drive to the motor.
Bypass connection
WARNING!
Never connect the supply power to the drive output terminals U2, V2
and W2. If frequent bypassing is required, employ mechanically connected switches
or contactors. Mains (line) voltage applied to the output can result in permanent
damage to the unit.
Before opening a contactor (DTC control mode selected)
Stop the drive and wait for the motor to stop before opening a contactor between the
output of the drive and the motor when the DTC control mode is selected. See the
appropriate
ACS800 Firmware Manual
for the required parameter settings.
Otherwise, the contactor will be damaged. In scalar control, the contactor can be
opened with the drive running.
Summary of Contents for ACS800-U7
Page 1: ...ACS800 Hardware Manual ACS800 07 Drives 45 to 560 kW ACS800 U7 Drives 50 to 600 hp ...
Page 4: ......
Page 28: ...Operation principle and hardware description 28 ...
Page 51: ...Planning the electrical installation 51 ...
Page 60: ...Planning the electrical installation 60 ...
Page 76: ...Electrical installation 76 ...
Page 84: ...Motor control and I O board RMIO 84 ...
Page 112: ...Maintenance 112 ...
Page 138: ...Dimensional drawings 138 Frame sizes R5 and R6 64778340_1 5 K ...
Page 139: ...Dimensional drawings 139 Frame sizes R7 and R8 68749930_1 7 C ...
Page 140: ...Dimensional drawings 140 IP54 and IP54R units of frame sizes R7 and R8 68749930_6 6 C ...
Page 148: ...3AFE64702165 Rev H EN 2012 09 19 Contact us www abb com drives www abb com drivespartners ...