Motor control and I/O board (RMIO)
What this chapter contains
This chapter shows
• external control connections to the RMIO board for the ACS800 Standard Control
Program (Factory Macro)
• specifications of the inputs and outputs of the board.
Note on optional terminal block X2
The connections for the RMIO board shown below apply also to optional terminal
block X2 available for the ACS800-07. The terminals of the RMIO board are wired to
terminal block X2 internally.
Terminals of X2 accept cables from 0.5 to 4.0 mm
2
(22 to 12 AWG). Tightening
torque for screw terminals is 0.4 to 0.8 Nm (0.3 to 0.6 lbf ft). For disconnecting wires
from spring terminals, use a screw driver with a blade thickness of 0.6 mm
(0.024 in.) and width of 3.5 mm (0.138 in.), for example, PHOENIX CONTACT SZF
1-0,6X3,5.
Note on terminal labelling
Optional modules (Rxxx) may have identical terminal designations with the RMIO
board.
Summary of Contents for ACS800-U7
Page 1: ...ACS800 Hardware Manual ACS800 07 Drives 45 to 560 kW ACS800 U7 Drives 50 to 600 hp ...
Page 4: ......
Page 28: ...Operation principle and hardware description 28 ...
Page 51: ...Planning the electrical installation 51 ...
Page 60: ...Planning the electrical installation 60 ...
Page 76: ...Electrical installation 76 ...
Page 84: ...Motor control and I O board RMIO 84 ...
Page 112: ...Maintenance 112 ...
Page 138: ...Dimensional drawings 138 Frame sizes R5 and R6 64778340_1 5 K ...
Page 139: ...Dimensional drawings 139 Frame sizes R7 and R8 68749930_1 7 C ...
Page 140: ...Dimensional drawings 140 IP54 and IP54R units of frame sizes R7 and R8 68749930_6 6 C ...
Page 148: ...3AFE64702165 Rev H EN 2012 09 19 Contact us www abb com drives www abb com drivespartners ...