Parameters 101
Selects the hexadecimal code of an event (warning, fault or
pure event) whose status is shown as bit 0 of
. The event codes are listed in chapter
(page
).
0000h
0000h…FFFFh
Code of event.
1 = 1
Specifies an auxiliary code for the event selected by the
previous parameter. The selected event is indicated by the
event word only if its auxiliary code matches the value of this
parameter.
With a value of 0000 0000h, the event word will indicate the
event regardless of the auxiliary code.
0000 0000h
0000 0000h …
FFFF FFFFh
Code of warning, fault or pure event.
1 = 1
Selects the hexadecimal code of an event (warning, fault or
pure event) whose status is shown as bit 1 of
. The event codes are listed in chapter
(page
).
0000h
0000h…FFFFh
Code of event.
1 = 1
Specifies an auxiliary code for the event selected by the
previous parameter. The selected event is indicated by the
event word only if its auxiliary code matches the value of this
parameter.
With a value of 0000 0000h, the event word will indicate the
event regardless of the auxiliary code.
0000 0000h
0000 0000h …
FFFF FFFFh
Code of warning, fault or pure event.
1 = 1
…
…
…
…
Selects the hexadecimal code of an event (warning, fault or
pure event) whose status is shown as bit 15 of
. The event codes are listed in chapter
(page
).
0000h
0000h…FFFFh
Code of event.
1 = 1
Specifies an auxiliary code for the event selected by the
previous parameter. The selected event is indicated by the
event word only if its auxiliary code matches the value of this
parameter.
With a value of 0000 0000h, the event word will indicate the
event regardless of the auxiliary code.
0000 0000h
0000 0000h …
FFFF FFFFh
Code of warning, fault or pure event.
1 = 1
05
Various run-time-type counters and measurements related to
drive maintenance.
All parameters in this group are read-only unless otherwise
noted.
On-time counter. The counter runs when the drive is powered. -
0…65535 d
On-time counter.
1 = 1 d
Motor run-time counter. The counter runs when the inverter
modulates.
-
0…65535 d
Motor run-time counter.
1 = 1 d
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...