104 Parameters
Drive status word 1.
This parameter is read-only.
-
0000h…FFFFh
Drive status word 1.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Bit
Name
Description
0
Enabled
) and start enable (
) signals are
present, and Drive interlock has not been activated.
Notes:
• In I/O or local control, clearing this bit makes the drive enter the
SWITCH-ON INHIBITED state (see page
• This bit is not affected by the presence of a fault.
1
Inhibited
1 = Start inhibited. See parameters
for the source of the
inhibiting signal.
2
DC charged 1 = DC circuit has been charged. If present, the DC switch is closed, and
charging switch is open.
0 = Charging not complete. If the inverter unit is not equipped with a DC
switch (F286), check setting of
3
Ready to
start
1 = Drive is ready to receive a start command
4
Following
reference
1 = Drive is ready to follow given reference
5
Started
1 = Drive has been started
6
Modulating
1 = Drive is modulating (output stage is being controlled)
7
Limiting
1 = Any operating limit (speed, torque, etc.) is active
8
Local control 1 = Drive is in local control
9
10
Ext1 active
1 = Control location EXT1 active
11
Ext2 active
1 = Control location EXT2 active
12
Reserved
13
Start request 1 = Start requested
Note:
At the time of publishing, a start request from the control panel does
not activate this bit if any start-inhibiting condition (see bit 1) is present.
14…15 Reserved
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...