144 Parameters
Constant time
The drive pre-magnetizes the motor before start. The pre-
magnetizing time is defined by parameter
. This mode should be selected if constant
pre-magnetizing time is required (e.g. if the motor start must
be synchronized with the release of a mechanical brake). This
setting also guarantees the highest possible break-away
torque when the pre-magnetizing time is set long enough.
WARNING!
The drive will start after the set
magnetizing time has passed even if motor
magnetization is not completed. In applications where
a full break-away torque is essential, ensure that the constant
magnetizing time is long enough to allow generation of full
magnetization and torque.
1
Automatic
Automatic start guarantees optimal motor start in most cases.
It includes the flying start function (starting into a rotating
motor) and the automatic restart function (a stopped motor
can be restarted immediately without waiting the motor flux to
die away). The drive motor control program identifies the flux
as well as the mechanical state of the motor and starts the
motor instantly under all conditions.
2
Defines the pre-magnetization time when
• parameter
(in
Vector motor control mode), or
• parameter
is set to
(in
scalar motor control mode).
After the start command, the drive automatically
premagnetizes the motor for the set time. To ensure full
magnetizing, set this parameter to the same value as, or
higher than, the rotor time constant. If not known, use the rule-
of-thumb value given in the table below:
Note:
This parameter cannot be changed while the drive is
running.
500 ms
0 … 10000 ms
Constant DC magnetizing time.
1 = 1 ms
Selects the way the motor is stopped when a stop command
is received.
Additional braking is possible by selecting flux braking (see
parameter
).
Note:
This parameter has no effect in a follower drive in a
master/follower configuration.
Coast
Stop by switching off the output semiconductors of the drive.
The motor coasts to a stop.
WARNING!
If a mechanical brake is used, ensure it is
safe to stop the drive by coasting.
0
Ramp
Stop along the active deceleration ramp. See parameter
group
on page
.
1
Torque limit
Stop according to torque limits (parameters
). 2
No.
Name/Value
Description
Def
/
FbEq16
Motor rated power
Constant magnetizing time
< 1 kW
> 50 to 100 ms
1 to 10 kW
> 100 to 200 ms
10 to 200 kW
> 200 to 1000 ms
200 to 1000 kW
> 1000 to 2000 ms
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...