158 Parameters
Defines acceleration time 1 as the time required for the speed
to change from zero to the speed defined by parameter
(
not
If the speed reference increases faster than the set
acceleration rate, the motor speed will follow the acceleration
rate.
If the speed reference increases slower than the set
acceleration rate, the motor speed will follow the reference.
If the acceleration time is set too short, the drive will
automatically prolong the acceleration in order not to exceed
the drive torque limits.
20.000 s
0.000 …1800.000 s Acceleration time 1.
10 = 1 s
Defines deceleration time 1 as the time required for the speed
to change from the speed defined by parameter
(
not
from parameter
) to zero.
If the speed reference decreases slower than the set
deceleration rate, the motor speed will follow the reference.
If the reference changes faster than the set deceleration rate,
the motor speed will follow the deceleration rate.
If the deceleration rate is set too short, the drive will
automatically prolong the deceleration in order not to exceed
drive torque limits (or not to exceed a safe DC link voltage). If
there is any doubt about the deceleration time being too short,
ensure that DC overvoltage control is on (parameter
).
Note:
If a short deceleration time is needed for a high inertia
application, the drive should be equipped with braking
equipment such as a brake chopper and brake resistor.
20.000 s
0.000 …1800.000 s Deceleration time 1.
10 = 1 s
Defines acceleration time 2. See parameter
60.000 s
0.000 …1800.000 s Acceleration time 2.
10 = 1 s
Defines deceleration time 2. See parameter
60.000 s
0.000 …1800.000 s Deceleration time 2.
10 = 1 s
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...