254 Parameters
…
are adapter module-specific. For
more information, see the documentation of the fieldbus
adapter module. Note that not all of these parameters are
necessarily in use.
-
0…65535
Fieldbus adapter configuration parameter.
1 = 1
…
…
…
…
See parameter
-
0…65535
Fieldbus adapter configuration parameter.
1 = 1
Validates any changed fieldbus adapter module configuration
settings. After refreshing, the value reverts automatically to
Note:
This parameter cannot be changed while the drive is
running.
Done
Refreshing done.
0
Refresh
Refreshing.
1
Displays the parameter table revision of the fieldbus adapter
module mapping file (stored in the memory of the drive).
In format axyz, where ax = major table revision number; yz =
minor table revision number.
This parameter is read-only.
-
Parameter table revision of adapter module.
-
Displays the drive type code in the fieldbus adapter module
mapping file (stored in the memory of the drive).
This parameter is read-only.
-
0…65535
Drive type code stored in the mapping file.
1 = 1
Displays the fieldbus adapter module mapping file revision
stored in the memory of the drive in decimal format.
This parameter is read-only.
-
0…65535
Mapping file revision.
1 = 1
Displays the status of the fieldbus adapter module
communication.
-
Not configured
Adapter is not configured.
0
Initializing
Adapter is initializing.
1
Time out
A timeout has occurred in the communication between the
adapter and the drive.
2
Configuration error
Adapter configuration error: mapping file not found in the file
system of the drive, or mapping file upload has failed more
than three times.
3
Off-line
Fieldbus communication is off-line.
4
On-line
Fieldbus communication is on-line, or fieldbus adapter has
been configured not to detect a communication break. For
more information, see the documentation of the fieldbus
adapter.
5
Reset
Adapter is performing a hardware reset.
6
Displays the patch and build versions of the adapter module
firmware in format xxyy, where xx = patch version number, yy
= build version number.
Example: C802 = 200.02 (patch version 200, build version 2).
Patch and build versions of adapter module firmware.
-
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...