28 Program features
Control interfaces
Programmable analog inputs
The control unit has two programmable analog inputs. Each of the inputs can be
independently set as a voltage (0/2…10 V or -10…10 V) or current (0/4…20 mA)
input by a jumper or switch on the control unit. Each input can be filtered, inverted
and scaled. The analog inputs on the control unit are read on a 0.5 ms time level.
The drive can be set to perform an action (for example, to generate a warning or fault)
if the value of an analog input moves out of a predefined range.
Settings
Parameter group
).
Programmable analog outputs
The control unit has two current (0…20 mA) analog outputs. Each output can be
filtered, inverted and scaled. The analog outputs on the control unit are updated on a
0.5 ms time level.
Settings
Parameter group
(page
).
Programmable digital inputs and outputs
The control unit has six digital inputs, a digital start interlock input, and two digital
input/outputs (I/O that can be set as either an input or an output). The digital inputs on
the control unit are read on a 0.5 ms time level.
One digital input (DI6) doubles as a PTC thermistor input. See section
Digital input/output DIO1 can be used as a frequency input, DIO2 as a frequency
output.
Settings
Parameter groups
(page
).
Programmable relay outputs
The control unit has three relay outputs. The signal to be indicated by the outputs can
be selected by parameters. The relay outputs on the control unit are updated on a 0.5
ms time level.
Settings
Parameter group
(page
).
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...