296 Parameters
is set to
, selects the user parameter set together with
parameter
Not selected
0.
0
Selected
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
DIO1
Digital input/output DIO1 (
, bit 0).
10
DIO2
Digital input/output DIO2 (
, bit 1).
11
-
See parameter
.
Defines the 1st priority external source for synchronization of
the drive’s time and date.
The date and time can also be directly set into
…
in which case this parameter is ignored.
Internal
No external source selected.
0
DDCS Controller
External controller.
1
Fieldbus A
Fieldbus interface A.
3
Embedded FB
Embedded fieldbus interface.
6
Panel link
Control panel, or Drive composer PC tool connected to the
control panel.
8
Ethernet tool link
Drive composer PC tool through an FENA module.
9
Number of full days passed since beginning of the year 1980.
This parameter, together with
makes it possible to
set the date and time in the drive via the parameter interface
from a fieldbus or application program. This may be
necessary if the fieldbus protocol does not support time
synchronization.
-
1…59999
Days since beginning of 1980.
1 = 1
No.
Name/Value
Description
Def
/
FbEq16
Status of source
defined by par.
Status of source
defined by par.
User parameter
set selected
0
0
Set 1
1
0
Set 2
0
1
Set 3
1
1
Set 4
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...