Parameters 305
Defines the stator resistance
R
S
of the motor model.
Resistance value is given at 20 °C.
0.00000 ohm
0.00000 …
100.00000 ohm
Stator resistance.
-
Defines the rotor resistance
R
R
of the motor model.
Resistance value is given at 20 °C.
Note:
This parameter is valid only for asynchronous motors.
0.00000 ohm
0.00000 …
100.00000 ohm
Rotor resistance.
-
Defines the main inductance
L
M
of the motor model.
Note:
This parameter is valid only for asynchronous motors.
0.00 mH
0.00 …100000.00
mH
Main inductance.
1 = 10 mH
Defines the leakage inductance
L
S
.
Note:
This parameter is valid only for asynchronous motors.
0.00 mH
0.00 …100000.00
mH
Leakage inductance.
1 = 10 mH
99
Motor configuration settings.
Selects the motor type.
Note:
This parameter cannot be changed while the drive is
running.
;
SynRM
(
95.21
b1);
Permanent
magnet
motor
(
95.21
b2)
Asynchronous
motor
Standard squirrel cage AC induction motor (asynchronous
induction motor).
0
Selects the motor control mode.
Note:
This parameter cannot be changed while the drive is
running.
Vector
Vector
Vector control. This mode is suitable for most applications.
Note:
Instead of direct torque control, scalar control is also
available, and should be used in the following situations:
• with multimotor applications 1) if the load is not equally
shared between the motors, 2) if the motors are of different
sizes, or 3) if the motors are going to be changed after the
motor identification (ID run)
• if the nominal current of the motor is less than 1/6 of the
nominal output current of the drive
• if the drive is used with no motor connected (for example,
for test purposes).
See also section
0
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...