Parameters 307
Defines the nominal motor speed. The setting must match the
value on the rating plate of the motor.
Note:
This parameter cannot be changed while the drive is
running.
0 rpm
0 … 6000 rpm
Nominal speed of the motor.
1 = 1 rpm
Defines the nominal motor power. The setting must match the
value on the rating plate of the motor. If nominal power is not
shown on the rating plate, nominal torque can be entered
instead in parameter
.
If multiple motors are connected to the drive, enter the total
power of the motors.
Note:
This parameter cannot be changed while the drive is
running.
0.00 kW
0.00 … 10000.00
kW
Nominal power of the motor.
1 = 1 unit
Defines the cosphi of the motor for a more accurate motor
model. The value is not obligatory, but is useful with an
asynchronous motor, especially when performing a standstill
identification run. With a permanent magnet or synchronous
reluctance motor, this value is not needed.
Notes:
• Do not enter an estimated value. If you do not know the
exact value, leave the parameter at zero.
• This parameter cannot be changed while the drive is
running.
0.00
0.00 … 1.00
Cosphi of the motor.
100 = 1
Defines the nominal motor shaft torque. This value can be
given instead of nominal power (
) if shown on the rating
plate of the motor.
Notes:
• This setting is an alternative to the nominal power value
takes priority.
• This parameter cannot be changed while the drive is
running.
0.000
N·m
0.000 …
4000000.000
N·m
Nominal motor torque.
1 = 1 unit
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...