310 Parameters
Switches the rotation direction of motor. This parameter can
be used if the motor turns in the wrong direction (for example,
because of the wrong phase order in the motor cable), and
correcting the cabling is considered impractical.
Notes:
• Changing this parameter does not affect speed reference
polarities, so positive speed reference will rotate the motor
forward. The phase order selection just ensures that
“forward” is in fact the correct direction.
• After changing this parameter, the sign of encoder
feedback (if any) must be checked. This can be done by
setting parameter
to
, and comparing the sign of
. If the sign of the
measurement is incorrect, the encoder wiring must be
corrected or the sign of
reversed.
• This parameter cannot be changed while the drive is
running.
U V W
Normal.
0
U W V
Reversed rotation direction.
1
No.
Name/Value
Description
Def
/
FbEq16
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...