378 Fault tracing
FF61
ID run
Motor ID run was not
completed successfully.
Check the nominal motor values in
parameter group
.
Check that no external control system is
connected to the drive.
Cycle the power to the drive (and its
control unit, if powered separately).
Check that the motor shaft is not locked.
Check the auxiliary code. The second
number of the code indicates the
problem (see actions for each code
below).
0001 Maximum current limit too low.
. Make sure that
>
Check that the drive is dimensioned
correctly according to the motor.
0002 Maximum speed limit or
calculated field weakening
point too low.
Check settings of parameters
•
•
•
•
•
Make sure that
•
) >
(0.50 × synchronous speed)
•
< 0, and
• supply voltage > (0.66 ×
0003 Maximum torque limit too low.
, and the torque limits in
group
Make sure that the maximum torque limit
in force is greater than 100%.
0004 Current measurement
calibration did not finish within
reasonable time.
Contact your local ABB representative.
0005…0008 Internal error.
Contact your local ABB representative.
0009 (Asynchronous motors only)
Acceleration did not finish
within reasonable time.
Contact your local ABB representative.
000A (Asynchronous motors only)
Deceleration did not finish
within reasonable time.
Contact your local ABB representative.
000B (Asynchronous motors only)
Speed dropped to zero during
ID run.
Contact your local ABB representative.
000E…0010 Internal error.
Contact your local ABB representative.
FF7E
Follower
A follower drive has tripped.
Check the auxiliary code. Add 2 to the
code to find out the node address of the
faulted drive.
Correct the fault in the follower drive.
Code
(hex)
Fault
Cause
What to do
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...