38 Program features
Example
A fan has vibrations in the range of 540 to 690 rpm and 1380 to 1560 rpm. To make
the drive avoid these speed ranges,
• enable the critical speeds function by turning on bit 0 of parameter
, and
• set the critical speed ranges as in the figure below.
Settings
(page
)
• Critical frequencies: parameters
(page
).
Speed controller autotune
The speed controller of the drive can be automatically adjusted using the autotune
function. Autotuning is based on an estimation of the mechanical time constant
(inertia) of the motor and machine.
The autotune routine will run the motor through a series of acceleration/deceleration
cycles, the number of which can be adjusted by parameter
. Higher values will produce more accurate results, especially if the difference
between initial and maximum speeds is small.
The maximum torque reference used during autotuning will be the initial torque (ie.
torque when the routine is activated) plus
, unless limited
by the maximum torque limit (parameter group
) or the nominal motor torque
(
). The calculated maximum speed during the routine is the initial speed
(ie. speed when the routine is activated) +
, unless limited
or
540
690
1380
1560
1
Par.
2
Par.
3
Par.
4
Par.
1
2
3
4
(rpm)
(output of function)
(rpm)
(input of function)
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...