394 Fieldbus control through the embedded fieldbus interface (EFB)
8
JOGGING_1
1
Accelerate to jogging 1 reference.
Notes:
• Bits 4…6 must be 0.
• See also section
).
0
Jogging 1 disabled.
9
JOGGING_2
1
Accelerate to jogging 2 reference.
See notes at bit 8.
0
Jogging 2 disabled.
10
REMOTE_
CMD
1
Fieldbus control enabled.
0
Control word and reference will not get through to the
drive, except for CW bits OFF1, OFF2 and OFF3.
11
EXT_CTRL_
LOC
1
Select External Control Location EXT2. Effective if the
control location is parameterized to be selected from the
fieldbus.
0
Select External Control Location EXT1. Effective if the
control location is parameterized to be selected from the
fieldbus.