402 Fieldbus control through the embedded fieldbus interface (EFB)
Exception codes
The table below shows the Modbus exception codes supported by the embedded
fieldbus interface.
2Bh / 0Eh
Encapsulated Interface
Transport
Supported subcodes:
• 0Eh Read Device Identification: Allows reading the
identification and other information.
Supported ID codes (access type):
• 00h: Request to get the basic device identification
(stream access)
• 04h: Request to get one specific identification
object (individual access)
Supported Object IDs:
• 00h: Vendor Name (“ABB”)
• 01h: Product Code (for example, “AINFX”)
• 02h: Major Minor Revision (combination of contents
of parameters
).
• 03h: Vendor URL (“www.abb.com”)
• 04h: Product name (for example, “ACS860”)
Code
Name
Description
01h
ILLEGAL FUNCTION
The function code received in the query is not an
allowable action for the server.
02h
ILLEGAL DATA
ADDRESS
The data address received in the query is not an
allowable address for the server.
03h
ILLEGAL DATA VALUE
The requested Quantity of Registers is larger than the
drive can handle.
Note:
This error does not mean that a value written to
a drive parameter is outside the valid range.
04h
SLAVE DEVICE
FAILURE
The value written to a drive parameter is outside the
valid range. See section
06h
SLAVE DEVICE BUSY
The server is engaged in processing a long-duration
program command.
Code
Function name
Description
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...