Program features 49
See also the block diagram on page
The jogging function operates on a 2 ms time level.
Notes:
• Jogging is not available when the drive is in local control.
• Jogging cannot be enabled when the drive start command is on, or the drive
started when jogging is enabled. Starting the drive after the jog enable switches
off requires a fresh start command.
8-9
0
1→0
0
Drive is stopped. As long as the jog enable signal is on, start
commands are ignored. After jog enable switches off, a fresh
start command is required.
9-10
x
0
1
Drive accelerates to the speed reference along the selected
acceleration ramp (parameters
).
10-11
x
0
1
Drive follows the speed reference.
11-12
x
0
0
Drive decelerates to zero speed along the selected
deceleration ramp (parameters
).
12-13
x
0
0
Drive is stopped.
13-14
x
0
1
Drive accelerates to the speed reference along the selected
acceleration ramp (parameters
).
14-15
x
0→1
1
Drive follows the speed reference. As long as the start
command is on, the jog enable signal is ignored. If the jog
enable signal is on when the start command switches off,
jogging is enabled immediately.
15-16
0→1
1
0
Start command switches off. The drive starts to decelerate
along the selected deceleration ramp (parameters
…
).
When the jog command switches on, the decelerating drive
adopts the deceleration ramp of the jogging function.
16-17
1
1
0
Drive follows the jog reference.
17-18
0
1→0
0
Drive decelerates along the deceleration ramp of the jogging
function.
18-19
0
0
0
Drive decelerates to zero speed along the selected
deceleration ramp (parameters
).
Phase
Jog
cmd
Jog
enable
Start
cmd
Description
Summary of Contents for ACS860
Page 1: ... ABB INDUSTRIAL DRIVES ACS860 primary control program Firmware manual ...
Page 4: ......
Page 10: ...10 Table of contents ...
Page 18: ...18 Using the control panel ...
Page 24: ...24 Control locations and operating modes ...
Page 54: ...54 Program features ...
Page 78: ...78 Program features ...
Page 90: ...90 Application macros ...
Page 342: ...342 Additional parameter data ...
Page 380: ...380 Fault tracing ...
Page 381: ...Fault tracing 381 ...
Page 382: ...382 Fault tracing ...
Page 436: ...436 Control chain diagrams ...