80 Application macros
Factory macro
The Factory macro is suited to relatively straightforward speed control applications
such as conveyors, pumps and fans, and test benches.
The drive is speed-controlled with the reference signal connected to analog input AI1.
The start/stop commands are given through digital input DI1; running direction is
determined by DI2. This macro uses control location EXT1.
Faults are reset through digital input DI3.
DI4 switches between acceleration/deceleration time sets 1 and 2. The acceleration
and deceleration times, as well as ramp shapes, are defined by parameters
DI5 activates constant speed 1.
Default parameter settings for the Factory macro
The default parameter settings for the Factory macro are listed under